Configuration Options
3-40
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Controlling and monitoring options
You can use the control feedback interface (PIQ) and feedback interface (PII) to
control and monitor the options with the user program.
Recommendation: Before you use the optional expansion of the ET 200S, check
using the feedback interface (see Table 3-10) whether all the configured electronic
modules are inserted.
Note
Using SFCs 14/15 it is possible to consistently access the control and feedback
interface.
The control and feedback interface is in the process image of the inputs and
outputs of the PM E 24-48 VDC or PM E 24-48 VDC/24-230 VAC power modules.
It is only available if you have selected the entries with the ending ...O or ...SO in
the configuration software for that power module (see also Appendix C).
There is one bit for each slot of the
electronic or RESERVE modules in the
ET 200S.
Control interface:
Slots 2 to 63
Feedback interface:
Slots 1 to 63
Bit no.
IB/QB x
IB/QB x+1
7
1
3
6 5 4
2
0
IB/QB x+2
IB/QB x+3
IB/QB x+4
IB/QB x+5
IB/QB x+6
IB/QB x+7
6
*
2
5 4 3
1
7
15 14
12
13
10
11
9 8
17
18
19
22 21 20
16
27
23
35
26
28
29
30
31
33
34
25 24
38
39
36
37
46
32
40
45
47
48
49
42
44 43
41
52 51
53
55 54
60
50
57
61
58
59
56
62
* Not applicable
63
Figure 3-11
Control (PIQ) and feedback interface (PII)
Control interface PIQ (AB x to AB x+7):
Using these bytes (8 bytes) you can control the diagnostic behavior of the slots
you have enabled in HWCONFIG for option handling.
Only the bits of the slots you have enabled at parameter assignment for option
handling are evaluated (they are marked with ”0”).
Содержание SIMATIC ET 200S
Страница 42: ...Product Overview 1 16 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 64: ...Brief Instructions on Commissioning ET 200S 2 22 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 112: ...Configuration Options 3 48 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 232: ...Commissioning and Diagnostics 6 72 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 244: ...General Technical Specifications 7 12 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 274: ...Interface Modules 8 30 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 538: ...4 IQ SENSE 13 18 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 564: ...Address Space of the Input and Outputs of the ET 200S C 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 574: ...Response Times D 10 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 580: ...Special Measures for Interference Free Operation F 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 600: ...Product Information on the Use of subassemblies modules in a Zone 2 Hazardous Area 2 A5E00352937 02 ...