Configuration Options
3-8
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Table 3-3
Interface modules and the applications for which they are suited
Applications
Interface module
•
Connecting the PROFIBUS DP by means of the
RS 485 interface
•
Use of fail-safe modules
•
Clocking as of 1.5 Mbps
•
Direct Data Exchange
•
The firmware can be updated via PROFIBUS DP
using HWCONFIG.
•
Operation as a DPV0 slave.
-- Acyclic data exchange (read/write data record):
class 2 services
•
Operation as a DPV1 slave.
-- Acyclic data exchange (read/write data record):
-- Diagnostics Interrupts
-- Process Alarms
-- Removal/Insertion Interrupt
•
Bus length of the ET 200S: max. 1 m (164 ft)
•
Number of modules: max. 63
Transmission rates:
9.6; 19.2; 45.45; 93.75;
187.5; 500 kbps,
1.5 ; 3; 6; 12 Mbps
IM151-1 HIGH
FEATURE
•
Connecting the PROFINET
•
Operation as I/O device
-- Start data records
-- Output data with provider status of the
I/O controller
-- Input data with provider status of the
I/O device
-- Diagnostics Interrupts
-- Process Alarms
-- Removal/Insertion Interrupt
•
Bus length of the ET 200S: max. 2 m (164 ft)
•
Number of modules: max. 63
•
Status byte for power modules
Transmission rate:
100 Mbps
Autosensing
IM151-3 PN
Содержание SIMATIC ET 200S
Страница 42: ...Product Overview 1 16 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 64: ...Brief Instructions on Commissioning ET 200S 2 22 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 112: ...Configuration Options 3 48 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 232: ...Commissioning and Diagnostics 6 72 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 244: ...General Technical Specifications 7 12 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 274: ...Interface Modules 8 30 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 538: ...4 IQ SENSE 13 18 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 564: ...Address Space of the Input and Outputs of the ET 200S C 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 574: ...Response Times D 10 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 580: ...Special Measures for Interference Free Operation F 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 600: ...Product Information on the Use of subassemblies modules in a Zone 2 Hazardous Area 2 A5E00352937 02 ...