Digital Electronic Modules
11-10
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Technical data
Dimensions and weight
Dimensions W x H x D (mm)
15 x 81 x 52
Weight
Approx. 35 g
Module-specific data
Number of inputs
2
Cable length
•
Unshielded
max. 600 m
(164 ft)
•
shielded
max. 1,000 m
(164 ft)
Voltages, currents, electrical potentials
Rated supply voltage (from
power module)
24 VDC
•
Polarity reversal
protection
Yes
Electrical isolation
•
Between the channels
No
•
Between channels and
backplane bus
Yes
Permissible potential differ-
ence
•
Between different circuits
75 VDC / 60 VAC
Insolation tested with
500 VDC
Current consumption
•
From power supply
Dependent on the
sensor
Power loss of the module
Typical 0.4 W
Status, interrupts, diagnostics
Status display
Green LED per
channel
Diagnostic functions
No
Sensor power supply output
Output voltage
•
Loaded
Min. L+ (--0.5 V)
Output current
•
Rated value
500 mA
•
Permitted range
0 to 500 mA
Data for selecting an sensor
Input voltage
•
Rated value
•
for ”1” signal
•
for ”0” signal
24 VDC
15 to 30 V
--30 to 5 V
Input current
•
For signal ”1”
Typ. 7 mA
(at 24 V)
Input delay
•
”0” to ”1” transition
Typ. 3 ms
(2.0 to 4.5 ms)
•
”1” to ”0” transition
Typ. 3 ms
(2.0 to 4.5 ms)
Input characteristic curve
To IEC 61131,
type 1
Connection of 2wire BEROs
possible
•
permitted quiescent
current
max. 1.5 mA
Содержание SIMATIC ET 200S
Страница 42: ...Product Overview 1 16 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 64: ...Brief Instructions on Commissioning ET 200S 2 22 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 112: ...Configuration Options 3 48 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 232: ...Commissioning and Diagnostics 6 72 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 244: ...General Technical Specifications 7 12 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 274: ...Interface Modules 8 30 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 538: ...4 IQ SENSE 13 18 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 564: ...Address Space of the Input and Outputs of the ET 200S C 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 574: ...Response Times D 10 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 580: ...Special Measures for Interference Free Operation F 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 600: ...Product Information on the Use of subassemblies modules in a Zone 2 Hazardous Area 2 A5E00352937 02 ...