Outputs
44
Siemens Building Technologies
Fire Safety & Security Products
07.2009
8.2.1 Unused
Unused
The output is by default not activated and not to use.
Exception: The “unused” output can be activated by the card reader [TM25].
8.2.2 External
Bell
External Bell
This output is activated in the event of the following states when the partition parameters are preset.
Partition mode:
Unset
Part set
Full set
Effects on the following events when the below partition parameter are preset:
1 X Tamper
alarm
1 X Burglar
alarm
X X X Panic
alarm
8
8
8
Fire alarm (pulsating 2 seconds)
9
9
Radio unset (0.5 seconds)
9
Radio full set (2 x 0.25 seconds)
9
Radio forced full set (4 x 0.25 seconds)
Partition parameters:
X =
Triggering is
always activated regardless of the set state.
1 =
Triggering only "When Part Set" in the partition parameters is chosen.
8 =
Triggering only if "By Fire" in the partition parameter is chosen.
9 =
Triggering only if "RF Confirm" in the partition parameter is chosen.
()= Activation of “Duration” (one time per partition) is defined in the menu partition.
8.2.3 Internal
Bell
Internal Bell
This output is activated in the event of the following states when the partition parameters are preset.
Partition mode:
Unset
Part set
Full set
Effects on the following events when the below partition parameter are preset:
X
2
Tamper
alarm
X
2
Burglar
alarm
X X X Panic
alarm
8
8
8
Fire alarm (pulsating 2 seconds)
Partition parameters:
X =
Triggering is
always activated regardless of the set state.
2 =
Triggering only "When Full Set" in the partition parameters is chosen.
8 =
Triggering only if "By Fire" in the partition parameter is chosen.
()= Activation of “Duration” (one time per partition) is defined in the menu partition.
8.2.4 Fire
Bell
Fire Bell
This output is activated regardless of the set state.
The “Fire Bell Duration” activation can be defined (per partition) in the partition parameters as either continu-
ous or pulsation (2 seconds)