Inputs
28
Siemens Building Technologies
Fire Safety & Security Products
07.2009
6.3.22 BA
24h
Burglar Alarm 24h
Brief description: BA 24H
Direct triggering on unset, part and full in the assigned partition.
Partition mode:
Unset
Part set
Full set
Effects on the following outputs when the below partition parameters are preset:
1
X
External
bell
X X 2 Internal
bell
1
X
Strobe
light
X
X
Cannot full set
X
Cannot part set
X X X Alarm
in
memory
X X X Burglar
alarm
X
X
Block lock not released
5 5 5 Buzzer
3
3
X
Burglar alarm system transmission line
3
3
X
Burglar alarm partition transmission line
3
3
X
Transmission line input
Partition parameters:
X =
Triggering regardless of the partition mode.
1 =
Triggering only if the external bell “When Part Set” in the partition parameter is chosen.
2 =
Triggering only if the internal bell “When Full Set” in the partition parameter is chosen.
3 =
Triggering only if "transmission" parameter is chosen.
5 =
Triggering only if “Buzzer On” in the keypad parameter is chosen.
6.3.23 Vault Sensor 24h (SI220 only)
Vault Sensor
(Seismic 24h)
Brief description: BA vault sensor; 24H
Direct triggering on unset, part and full set in the assigned partition.
This input reacts like a 24H burglar alarm line. If, however, an input is programmed to this function, the
“Vibration” output is set for 5 seconds in a random time of between 30 and 90 minutes
With this output, the test generator for structure-borne sound generator can now be triggered in order to
test the alarm inputs of vault sensors. If this input does not trigger after the output has been set, this is
detected by the central control unit which generates a fault (not an alarm).
This means that this type of input operates only in conjunction with a “Vault Sensor” test output.
Содержание SI120
Страница 99: ......