13.7.3 Test
Periodicity
[TM73]Test period
This parameter defines the time interval between two test calls, or between the last transmission and the last
call. The test period programmed in Receiver 1 act only on the "Auto test 1" transmission line. Any number
between 000 and 999 can be entered. This number multiplied by ½ hour gives the time interval, with 000 =
Test switched off.
Example
:
z
Time interval ½ hour ->
Value 001
z
Time interval 1 hour ->
Value 002
z
Time interval 1½ hours -> Value 003
z
Time interval 2 hours ->
Value 004
z
Time interval 3 hours ->
Value 006
z
Time interval 5 hours ->
Value 010
z
Time interval 8 hours ->
Value 016
z
Time interval 10 hours -> Value 020
z
Time interval 12 hours -> Value 024
z
Time interval 18 hours -> Value 036
z
Time interval 24 hours -> Value 048
z
Time interval 36 hours -> Value 072
z
Time interval 48 hours -> Value 096
z
Time interval 72 hours -> Value 144
Auto Test 1 / 2 in
The offset (start) of the test call is defined in the menu miscellaneous "Auto Test 1 / 2 in”
Important:
An already programmed offset is not reacted to after changing or confirming the test period. If an
offset is required, this must be programmed after programming the test period.
Start time
The sequence of programming the test period and the offset are important for the start time. The start times
for the first test are shown in the following table, with the autotest being programmed first.
Autotest, period
changed / confirmed
Offset
Hrs./min.
Start time of first test
No
-
After end of current time interval
Yes
-
1 minute after leaving the engineer menu,
then after time interval.
Yes / No
00H 00M
Time interval starts after confirmation of
offset Þ first test after time interval
Yes / No
02H 00M
2 hours after confirmation of offset,
then after time interval
13.8 ARC Remote Access PIN
*Account code
Allows to set if an Access Code for the remote access is needed.
Allows to set the default value of the transmission code for all inputs. This function works with CESA 200,
free contact ID and VDS protocols.
13.9 ARC Remote Access Code
Code for alarm verifica-
tion
This parameter can be activated if access for audio verification is to take place only by means of a code.
For this, a 6-digit number can be entered. This must then always be entered before access.