Partitions
56
Siemens Building Technologies
Fire Safety & Security Products
07.2009
9.6.1
Fire Bell Duration
Fire Bell Duration
This parameter defines the maximum triggering time of the fire bell output in the event of a fire warning
alarm. Times from 000 to 127 seconds or minutes can be entered (000 = continuous).
This timer runs only for outputs with logical type “Fire Bell” and not for “External Bell” or “Internal Bell”
9.7 Strobe
Duration
Strobe Duration
This parameter defines the maximum triggering time of the strobe light outputs in the event of an alarm.
Times from 000 to 127 second or minutes can be entered (000 = continuous).
9.8 Emercency
Exit
Emergency Exit Dura-
tion
This parameter defines the maximum triggering time of the emergency exit.
Times from 000 to 127 seconds or minutes can be entered (000 = continuous).
9.9 Engineer
Reset
[TM4] Engineer Reset
This parameter defines whether or not the partition is subject to the engineer reset defined in the main menu
Requested
= Engineer reset authorized
No =
No
engineer
reset
9.10 Set
possible
The first parameter defines whether the partition can be set or not without previous
resetting of the alarm memory. In this case the memory is automatically reset on
setting.The other three parameters select whether or not the partition can be set
despite an existing battery fault, mains failure or telephone line
fault.
Setting with
Battery Failure
This parameter defines whether or not the partition can be set despite an existing battery fault.
B = Setting authorized if battery failure
- = Setting not authorized
Setting with
Mains Failure
This parameter defines whether or not the partition can be set despite an existing mains fault.
M = Setting authorized if mains failure
- = Setting not authorized
Setting with
Line Failure
The parameter defines whether or not the partition can be set despite the existence of a telephone line fault.
L = Setting authorized if line failure
- = Setting not authorized
9.11 Setting with Alarm in Memory
This parameter defines whether the partition can be set or not without previous re-
setting of the alarm memory. In this case the memory is automatically reset on set-
ting.
Setting with
Alarm in Memory
possible
= Setting authorized if alarm in memory
impossible = Setting not authorized