Inputs
31
Siemens Building Technologies
Fire Safety & Security Products
07.2009
6.3.28 BA Entry/Exit Full or Part Set
Burglar Alarm Full/Part
Set, Entry/Exit
Brief description: BA external delay; Internal delay
On part set: Delayed entry and exit triggering in the assigned partition.
On full set: Delayed entry and exit triggering in the assigned partition.
DE, UK
If the input remains triggered up the end of the delay time, the partition is again unset.
All other country versions
If the input remains triggered up the end of the delay time, the partition remains full set and an alarm is
triggered.
Partition mode:
Unset
Part set
Full set
Effects on the following outputs when the below partition parameters are
preset:
1 / 7
7 External
bell
7 2 / 7
Internal bell
1 / 7
7 Strobe
light
7
7
Alarm in memory
X
X
Block lock not released
5 5 Buzzer
3 / 7
7
Burglar alarm system transmission line
3 / 7
7
Burglar alarm partition transmission line
3 / 7
7
Transmission line input
Partition parameters:
X =
Triggering regardless of the partition mode.
1 =
Triggering only if the external bell “When Part Set” in the partition parameter is chosen.
2 =
Triggering only if the internal bell “When Full Set” in the partition parameter is chosen.
3 =
Triggering only if "transmission" parameter is chosen.
5 =
Triggering only if “Buzzer On” in the keypad parameter is chosen.
7 =
Triggering only after delay.
6.3.29 BA Exit Terminator Full Set only
Full Set Time Abort
Brief description: BA external delay, exit termination; internal inactive
On part set: No triggering in the assigned partition.
On full set: Leaving the house, this input has to be closed within the “delay time” (000 to 127 min-
utes/seconds) otherwise an immediate alarm will be triggered. The exit termination will also stop the delay
time and set the partition in full set state.
Entering the house, this input will start the “delay time”, when the delay time is lapsed an immediate alarm
will be triggered.
A typical application is a magnetic contact at the entrance door or a locking bolt.
DE, UK
If one of the delayed inputs is triggered, when the contact is closed, the partition changes to unset state with
no alarm.
All other country ver-
sions
If one of the delayed inputs is triggered, when the contact is closed, the partition changes to full set state with
an immediate alarm.
Input triggered Þ Burglar alarm in the assigned partition.
Partition mode:
Unset
Part set
Full set
Effects on the following outputs when the below partition parameters are preset:
7
External
bell
7
Strobe
light
7
Alarm in memory
5
Buzzer
7
Burglar alarm system transmission line
7
Burglar alarm partition transmission line
7
Transmission line input
Partition parameters: