Siemens Building Technologies
SED2 variable speed drives
CM1U5192en
HVAC Products
Programming
01.2002
P0718
CO/BO: Hand / Auto
Selects function of digital input 8 (via analog input)
Unit: -
Min: 0
Def: 0
Max: 1
Level 3
r0722
CO/BO: Binary input values
Displays status of digital inputs.
Unit: -
Min: -
Def: -
Max: -
Level 3
Bit fields:
Bit00
Digital input 1
0
OFF, 1
ON
Bit01
Digital input 2
0
OFF, 1
ON
Bit02
Digital input 3
0
OFF, 1
ON
Bit03
Digital input 4
0
OFF, 1
ON
Bit04
Digital input 5
0
OFF, 1
ON
Bit05
Digital input 6
0
OFF, 1
ON
Bit06
Digital input 7 (via ADC 1)
0
OFF, 1
ON
Bit07
Digital input 8 (via ADC 2)
0
OFF, 1
ON
Note:
Segment is lit when signal is active.
P0725
PNP / NPN digital inputs
Switches between active high (PNP) and active low (NPN). This is valid for all digital inputs
simultaneously.
The following is valid by using the internal supply:
Unit: -
Min: 0
Def: 1
Max: 1
Level 3
Settings:
0=NPN mode ==> low active
1=PNP mode ==> high active
P0731[2]
BI: Function of digital output 1
Defines source of digital output 1.
Unit: -
Min: 0.0
Def: 52.3
Max: 4000.0
Level 2
Settings:
52.0
Drive ready
0 Closed
52.1
Drive ready to run
0 Closed
52.2
Drive running
0 Closed
52.3
Drive fault active
0 Closed
52.4
OFF2 active
1 Closed
52.5
OFF3 active
1 Closed
52.6
Switch on inhibit active
0 Closed
52.7
Drive warning active
0 Closed
52.8
Deviation setpoint/actual value
1 Closed
52.9
PZD control (Process Data Control) 0 Closed
52.A
Maximum frequency reached
0 Closed
52.B
Warning: Motor current limit
1 Closed
52.C
Motor holding brake (MHB) active
0 Closed
52.D
Motor overload
1 Closed
52.E
Motor running direction right
0 Closed
52.F
VSD drive overload
1 Closed
53.0
DC brake active
0 Closed
53.1
VSD frequency less switch off limit
0 Closed
53.2
VSD frequency less minimum freq.
0 Closed
53.3
Current greater or equal than limit
0 Closed
53.4
Act. freq. greater comparison freq.
0 Closed
53.5
Act. freq. less comparison freq.
0 Closed
53.6
Act. freq. greater/equal setpoint
0 Closed
53.7
Voltage less than threshold
0 Closed
53.8
Voltage greater than threshold
0 Closed
53.A
PID output at lower limit (P2292)
0 Closed
53.B
PID output at upper limit (P2291)
0 Closed
Index:
P0731[0] : 1st command data set (CDS)
P0731[1] : 2nd command data set (CDS)
P0732[2]
BI: Function of digital output 2
Defines source of digital output 2.
Unit: -
Min: 0.0
Def: 52.2
Max: 4000.0
Level 2
Details:
See P0731 (function of digital output 1).
r0747
CO/BO: State of digital outputs
Displays status of digital outputs (also includes inversion of digital outputs via P0748).
Unit: -
Min: -
Def: -
Max: -
Level 3
Bit fields:
Bit00
Digital output 1 energized
0
NO, 1
YES
Bit01
Digital output 2 energized
0
NO, 1
YES
Dependency:
Bit 0= Relay de-energized / contacts open
Bit 1= Relay energized / contacts closed
P0748
Invert digital outputs
Defines high and low states of relay for a given function.
Unit: -
Min: 0
Def: 0
Max: 7
Level 3
Bit fields:
Bit00
Invert digital output 1
0
NO, 1
YES
Bit01
Invert digital output 2
0
NO, 1
YES
r0752[2]
Act. input of ADC [V] or [mA]
Displays smoothed analog input value in volts before the characteristic block.
Unit: -
Min: -
Def: -
Max: -
Level 2
Index:
r0752[0] : Analog input 1 (ADC 1)
r0752[1] : Analog input 2 (ADC 2)
P0753[2]
Smooth time ADC
Defines filter time (PT1 filter) in [ms] for analog input.
Unit: ms
Min: 0
Def: 100
Max: 10000
Level 3
Index:
P0753[0] : Analog input 1 (ADC 1)
P0753[1] : Analog input 2 (ADC
Note:
Increasing this time (smooth) reduces jitter but slows down response to the analog input.
r0754[2]
Act. ADC value after scaling [%]
Shows smoothed value of analog input in [%] after scaling block.
Unit: %
Min: -
Def: -
Max: -
Level 2
Index:
r0754[0] : Analog input 1 (ADC 1)
r0754[1] : Analog input 2 (ADC 2)
Dependency:
P0757 to P0760 define range (ADC scaling)
Содержание SED2 Series
Страница 2: ...2 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products 01 2002 ...
Страница 10: ...10 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Introduction 01 2002 ...
Страница 52: ...52 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Commissioning 01 2002 ...
Страница 125: ...125 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en Landis Staefa Division Index 01 2002 ...