42/126
Siemens Building Technologies
SED2 variable speed drives
CM1U5192en
HVAC Products
Commissioning
01.2002
5.1.1
DIP switch settings
For all versions of the SED2, the DIP switches used to configure the analog inputs are
located on the I/O module. The I/O module is located under the operator panel, to
which it is connected either directly (frame sizes A to C, IP20) or via a cable (frame
sizes D to E, and all IP54 models).
2 0
2 1 2 2 2 3
2 4
2 5
2 9
3 0
1 7
2 6 2 7 2 8
1 2
1 3 1 4
1 5 1 6
1 0
1 1
6
7
8
9
1
2
3
4
5
ON
1 2
ON
1
2
DIP switches for
analog inputs
DIP switches
for setting
mains frequency
51
92
Z
13
e
n
I/O module
SED2 frame size A
In all versions of the SED2, the DIP switches for setting the mains frequency and
selecting US or European units of measurement are located on the control board under
the I/O module.
5.1.1.1
Setting the DIP switches on the I/O module
♦
DIP switch 1
Analog input 1:
OFF position:
Voltage 0 to 10 V
ON position:
Current 0 to 20 mA
♦
DIP switch 2
Analog input 2:
OFF position:
Voltage 0 to 10 V
ON position:
Current 0 to 20 mA
Factory setting for both DIP switches: OFF = Voltage 0 to 10 V.
5.1.1.2
DIP switch settings on the control board
♦
DIP switch 2:
OFF position:
European default settings (50 Hz, kW etc.).
ON position:
North American default settings (60 Hz, hp, etc.).
Factory setting: OFF = 50 Hz.
♦
DIP switch 1
Not for customer use. This switch must be in the OFF position for
correct functioning of the VSD.
Location of the
DIP switches
Содержание SED2 Series
Страница 2: ...2 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products 01 2002 ...
Страница 10: ...10 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Introduction 01 2002 ...
Страница 52: ...52 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Commissioning 01 2002 ...
Страница 125: ...125 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en Landis Staefa Division Index 01 2002 ...