96/126
Siemens Building Technologies
SED2 variable speed drives
CM1U5192en
HVAC Products
Programming
01.2002
P2009[2]
USS normalization
Min: 0
Def: 0
Max: 1
Level 3
Settings:
0=Disabled
1=Enabled
Index:
P2009[0] : Serial interface COM link
P2009[1] : Serial interface BOP link
Note:
If enabled, the main setpoint (word 2 in PZD) is not interpreted as 100 %=4000H, but as "absolute" instead (e.g.
4000H=16384 means 163.84 Hz ).
P2010[2]
USS baudrate
Sets baud rate for USS communication.
Unit: -
Min: 4
Def: 6
Max: 12
Level 3
Settings:
4= 2400 baud
5= 4800 baud
6= 9600 baud
7= 19200 baud
8= 38400 baud
9= 57600 baud
10=76800 baud
11= 93750 baud
12= 115200 baud
Index:
P2010[0] : Serial interface COM link
P2010[1] : Serial interface BOP link
P2011[2]
USS address
Sets a unique address for variable speed drive.
Unit: -
Min: 0
Def: 0
Max: 31
Level 3
Index:
P2011[0] : Serial interface COM link
P2011[1] : Serial interface BOP link
Note:
You can connect up to a further 30 variable speed drives via the serial link (i.e. 31 variable speed drives in total) and
control them with the USS serial bus protocol.
P2014[2]
USS telegram off time
Defines a time T_off after which a fault will be generated (F0070) if no telegram is received via
the USS channels.
Unit: ms
Min: 0
Def: 0
Max: 65535
Level 3
Index:
P2014[0] : Serial interface COM link
P2014[1] : Serial interface BOP link
Note:
By default (time set to 0), no fault is generated (i.e. watchdog disabled).
P2040
CB telegram off time
Defines time after which a fault will be generated (F0070) if no telegram is received via the link (SOL).
Unit: ms
Min: 0
Def: 20
Max: 65535
Level 3
Dependency:
Setting 0=watchdog disabled
P2041[5]
CB parameter
Configures a communication board (CB).
Unit: -
Min: 0
Def: 0
Max: 65535
Level 3
Index:
P2041[0] : CB parameter 0
P2041[1] : CB parameter 1
P2041[2] : CB parameter 2
P2041[3] : CB parameter 3
P2041[4] : CB parameter 4
Note:
See relevant communication board manual for protocol definition and appropriate settings
r2050[8]
CO: PZD from CB
Displays PZD received from communication board (CB).
Unit: -
Min: -
Def: -
Max: -
Level 3
Index:
r2050[0] : Received word 0
r2050[1] : Received word 1
r2050[2] : Received word 2
r2050[3] : Received word 3
r2050[4] : Received word 4
r2050[5] : Received word 5
r2050[6] : Received word 6
r2050[7] : Received word 7
Note:
The control words can be viewed as bit parameters r2032 and r2033.
P2051[8]
CI: PZD to CB
Connects PZD to CB.
This parameter allows the user to define the source of status words and actual values for the
reply PZD.
Unit: -
Min: 0:0
Def: 52:0
Max: 4000:0
Level 3
Settings:
Status word 1=52
CO/BO: Act. status word 1 (see r0052)
Actual value 1= 21 variable speed drive output frequency (see r0021)
Other BICO settings are possible
Index:
P2051[0] : Transmitted word 0
P2051[1] : Transmitted word 1
P2051[2] : Transmitted word 2
P2051[3] : Transmitted word 3
P2051[4] : Transmitted word 4
P2051[5] : Transmitted word 5
P2051[6] : Transmitted word 6
P2051[7] : Transmitted word 7
r2053[5]
CB identification
Displays identification data of the communication board (CB). The different CB types (r2053[0])
are given in the Enum declaration.
Unit: -
Min: -
Def: -
Max: -
Level 3
Settings:
0=No CB option board
1=PROFIBUS DP
2=DeviceNet
56 not defined
Index:
r2053[0] : CB type (PROFIBUS=1)
r2053[1] : Firmware version
r2053[2] : Firmware version detail
r2053[3] : Firmware date (year)
r2053[4] : Firmware date (day/month)
r2054[7]
CB diagnosis
Displays diagnostic information of communication board (CB).
Unit: -
Min: -
Def: -
Max: -
Level 3
Index:
r2054[0] : CB diagnosis 0
r2054[1] : CB diagnosis 1
r2054[2] : CB diagnosis 2
r2054[3] : CB diagnosis 3
r2054[4] : CB diagnosis 4
r2054[5] : CB diagnosis 5
r2054[6] : CB diagnosis 6
Содержание SED2 Series
Страница 2: ...2 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products 01 2002 ...
Страница 10: ...10 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Introduction 01 2002 ...
Страница 52: ...52 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Commissioning 01 2002 ...
Страница 125: ...125 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en Landis Staefa Division Index 01 2002 ...