98/126
Siemens Building Technologies
SED2 variable speed drives
CM1U5192en
HVAC Products
Programming
01.2002
Unit: Hz
Min: 0.00
Def: 50.00
Max: 650.00
Details:
Sets a threshold F3 for comparing actual torque to torque the envelope for belt failure detection.
Note:
See P2182 (belt threshold frequency 1).
P2185,
P2187, P2189
Upper torque threshold 1, 2, and 3
Upper limit threshold value 1 for comparing actual torque.
Unit: Nm
Min: 0.0
Def: 99999.0
Max: 99999.0
Level 3
Details:
Upper limit threshold value for comparing actual torque.
Note:
See P2182 (belt threshold frequency).
P2186,
P2188, P2190
Lower torque threshold 1, 2, and 3
Lower limit threshold value 1 for comparing actual torque.
Unit: Nm
Min: 0.0
Def: 0.0
Max: 99999.0
Level 3
Details:
Lower limit threshold value for comparing actual torque.
Note:
See P2182 (belt threshold frequency).
P2191
Belt failure speed tolerance
P2191 defines the allowed speed variation bandwidth between the variable speed drive
frequency, and the speed reference from the pulse train. When the speed of the driven
machine varies by more than this amount, a trip or warning is given.
Unit: Hz
Min: 0.00
Def: 3.00
Max: 20.00
Level 3
Details:
P2191 defines the allowed speed variation bandwidth between the variable speed drive frequency, and the speed
reference from the pulse train. When the speed of the driven machine varies by more than this amount, a trip or warning
is given.
P2192
Time delay for belt failure
P2192 defines a delay before warning/trip becomes active. It is used to eliminate events
caused by transient conditions. It is used for both methods of fault detection.
Unit: s
Min: 0
Def: 10
Max: 65
Level 3
Details:
P2192 defines a delay before warning/trip becomes active. It is used to eliminate events caused by transient conditions.
It is used for both methods of fault detection.
r2197
CO/BO: Monitoring word 1
Monitoring word 1 which indicates the state of monitor functions. Each bit represents one
monitor function.
Unit: -
Min: -
Def: -
Max: -
Level 3
Bit fields:
Bit00
Act. freq. r0024
<=
P1080
0
NO, 1
YES
Bit01
Act. freq. r0024
<=
P2155
0
NO, 1
YES
Bit02
Act. freq. r0024
>
P2155
0
NO, 1
YES
Bit03
Act. freq. r0024
>
zero
0
NO, 1
YES
Bit04
Act. freq. r0024
>=
setp.
0
NO, 1
YES
Bit05
Act. freq. r0024
<=
P2167
0
NO, 1
YES
Bit06
Act. freq. r0024
>=
P1082
0
NO, 1
YES
Bit07
Act. freq. r0024
==
setp.
0
NO, 1
YES
Bit08
Act. current r0068 >= P2170
0
NO, 1
YES
Bit09
Act. unfilt. Vdc
<
P2172
0
NO, 1
YES
Bit10
Act. unfilt. Vdc
>
P2172
0
NO, 1
YES
Bit11
No load condition
0
NO, 1
YES
r2198
CO/BO: Monitoring word 2
Monitoring word 2 which indicates the state of monitor functions. Each bit represents one
monitor function.
Unit: -
Min: -
Def: -
Max: -
Level 3
Bit fields:
Bit00
| n,filtered r2169 | < P2157
0
NO, 1
YES
Bit01
| n,filtered r2169 | > P2157
0
NO, 1
YES
Bit02
| n,filtered r2169 | < P2159
0
NO, 1
YES
Bit03
| n,filtered r2169 | > P2159
0
NO, 1
YES
Bit04
| n,set | < P2161
0
NO, 1
YES
Bit05
n,set > 0
0
NO, 1
YES
Bit06
Motor blocked
0
NO, 1
YES
Bit07
Motor stalled
0
NO, 1
YES
Bit08
| I,act r0068 | < P2170
0
NO, 1
YES
Bit09
|T,act| > P2174 & setpoint reached
0
NO, 1
YES
Bit10
| T,act | > P2174
0
NO, 1
YES
Bit11
Belt failure warning
0
NO, 1
YES
Bit12
Belt failure trip
0
NO, 1
YES
P2200[2]
BI: Enable PID controller
The PID mode allows the user to enable/disable the PID controller. Setting to 1 enables the
PID closed-loop controller.
Unit: -
Min: 0:0
Def: 0:0
Max: 4000:0
Level 2
Details:
PID mode Allows user to enable/disable the PID controller. Setting to 1 enables the PID closed-loop controller.
Index:
P2200[0] : 1st command data set (CDS)
P2200[1] : 2nd command data set (CDS)
Dependency:
Setting 1 automatically disables normal ramp times set in P1120 and P1121 and the normal frequency setpoints.
Following an OFF1 or OFF3 command, however, the variable speed drive frequency will ramp down to zero using the
ramp time set in P1121 (P1135 for OFF3).
Содержание SED2 Series
Страница 2: ...2 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products 01 2002 ...
Страница 10: ...10 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Introduction 01 2002 ...
Страница 52: ...52 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Commissioning 01 2002 ...
Страница 125: ...125 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en Landis Staefa Division Index 01 2002 ...