24/126
Siemens Building Technologies
SED2 variable speed drives
CM1U5192en
HVAC Products
Electrical installation
01.2002
L1
L2
L3
PE
BMS
SED2
w
v
u
51
92
Z04
en
Min. 16 mm²
(4 AWG)...
compensating cable
Install all cables on the
same side of the plate
Min.200 mm
(7.8 inches)....
between
control cables,
motor cables and
mains cables
Motor cable
Mains power supply
Min.10 mm² (6 AWG)...
PE: min.10 mm² (6 AWG)...
Remove cable
insulation
Control cables
Grounding rail
Motor
51
9
2
J
1
0
1
L1
L2
L3
2
6
3
4
5
1
Incoming mains cable
2
Control cable
3
Motor cable
4
Footprint filter
5
Metal backplate
6
Use suitable cable clamps to
ensure good conductive
contact between the shield of
the motor and control cables
and the metal backplate
7
Connect the motor cable
shield to
.
Cable routing for frame
sizes A to C, with
footprint filter