77/126
Siemens Building Technologies
SED2 variable speed drives
CM1U5192en
HVAC Products
Programming
01.2002
6.5 System parameter list for levels 1 to 3
r0000
Drive display
Displays the user selected output as defined in P0005.
Unit: -
Min: -
Def: -
Max: -
Level 1
Note:
Pressing the "Fn" button for 2 seconds allows the user to view the values of DC link voltage, output current, output
frequency, and chosen r0000 setting (defined in P0005).
r0002
Drive state
Displays actual drive state.
Unit: -
Min: -
Def: -
Max: -
Level 3
Settings:
0=Commissioning mode (P0010=0)
1=Drive ready
2=Drive fault active
3=Drive starting (DC link precharging)
4=Drive running
5=Stopping (ramping down)
Dependency:
State 3 visible only while precharging DC link, and when externally powered communications board is fitted.
P0003
User access level
Defines user access level to parameter sets. The default setting (standard) is sufficient for most
simple applications.
Unit: --
Min: 0
Def: 1
Max: 4
Level 1
Settings:
0=User defined parameter list - see P0013 for details
1=Standard: Access into frequently used parameters.
2=Extended: Access to e.g. variable speed drive I/O
functions.
3=Expert: For experienced users only
4=Service: Only for use by authorized service personal -
P0004
Parameter filter
Filters available parameters according to functionality to enable a more focussed approach to
commissioning.
Unit: -
Min: 0
Def: 0
Max: 22
Level 1
Example:
P0004=22 specifies that only PID parameters will be visible.
Settings:
0=All parameters
2=Variable speed drive
3=Motor
4=Speed sensor
5=Technol. application/units
7=Commands, binary I/O
8=ADC and DAC
10 =Setpoint channel / RFG
12 =Drive features
13 =Motor control
20 =Communication
21 =Alarms / warnings / monitoring
22 =Technology controller (e.g. PID)
Dependency:
Parameters marked "Quick Comm: Yes" in the parameter header can only be set when P0010=1 (Quick
Commissioning).
Note:
The variable speed drive will start with any setting of P0004.
P0005
Display selection
Selects display for parameter r0000 (drive display).
Unit: -
Min: 2
Def: 21
Max: 2294
Level 2
Settings:
21=Actual frequency
25=Output voltage
26=DC link voltage
27=Output current
Note:
These settings refer to read only parameter numbers ("rxxxx").
Details:
See relevant "rxxxx" parameter descriptions.
P0006
Display mode
Defines mode of display for r0000 (drive display).
Unit: -
Min: 0
Def: 2
Max: 4
Level 3
Settings: 0=In Ready state alternate between setpoint and output
frequency. During run, display output frequency.
1=In Ready state display setpoint. In run display output freq.
2=In Ready state alternate between P0005 value and r0020
value. In run display P0005 value
3=In Ready state alternate between r0002 value and
r0020 value. In run display r0002 value
4=In all states just display P0005
Note:
When variable speed drive is not running, the display alternates between the values for "Not Running" and "Running".
Per default, the setpoint and actual frequency values are displayed alternately.
P0010
Commissioning parameter filter
Filters parameters so that only those related to a particular functional group are selected.
Unit: -
Min: 0
Def: 0
Max: 30
Level 1
Settings:
0=Ready
1=Quick commissioning
2=Variable speed drive
29 =Download
30 =Factory setting
Dependency:
Reset to 0 for variable speed drive to run.
P0003 (user access level) also determines access to parameters.
Note:
If P3900 is not 0 (0 is the default value), this parameter is automatically reset to 0.
P0011
Lock for user-defined parameter
Unit: -
Min: 0
Def: 0
Max: 65535
Level 3
Details:
See P0013 (user-defined parameter).
P0012
Key for user-defined parameter
Unit: -
Min: 0
Def: 0
Max: 65535
Level 3
Details:
See P0013 (user-defined parameter).
P0013[20]
User-defined parameter
Defines a limited set of parameters to which the end user will have access.
Unit: -
Min: 0
Def: 0
Max: 65535
Level 3
Содержание SED2 Series
Страница 2: ...2 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products 01 2002 ...
Страница 10: ...10 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Introduction 01 2002 ...
Страница 52: ...52 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Commissioning 01 2002 ...
Страница 125: ...125 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en Landis Staefa Division Index 01 2002 ...