78/126
Siemens Building Technologies
SED2 variable speed drives
CM1U5192en
HVAC Products
Programming
01.2002
Instructions:
1. Step 1: Set P0003=3 (expert user)
2. Step 2: Go to P0013 indices 0 to 16 (user list)
3. Step 3: Enter into P0013 index 0 to 16 the parameters required to be visible in the user-defined list. The following
values are fixed and cannot be changed:
- P0013 index 19=12 (key for user defined parameter)
- P0013 index 18=10 (commissioning parameter filter)
- P0013 index 17= 3 (user access level)
4. Step 4: Set P0003=0 to activate the user defined parameter.
Dependency:
First, set P0011 ("lock") to a different value than P0012 ("key") to prevent changes to user-defined parameter. Then, set
P0003 to 0 to activate the user-defined list.
When locked and the user-defined parameter is activated, the only way to exit the user-defined parameter (and view
other parameters) is to set P0012 ("key") to the value in P0011 ("lock").
Note:
Alternatively, set P0010=30 (commissioning parameter filter=factory setting) and P0970=1 (factory reset) to perform a
complete factory reset. The default values of P0011 ("lock") and P0012 ("key") are the same.
r0018
Firmware version
Displays version number of installed firmware.
Unit: -
Min: -
Def: -
Max: -
Level 3
r0019
CO/BO: BOP control word
Displays status of operator panel commands.
The settings below are used as the "source" codes for keypad control when connecting to
BICO input parameters.
Unit: -
Min: -
Def: -
Max: -
Level 3
Bit fields:
Bit00
ON/OFF1
0
NO,
1
YES
Bit01
OFF2: Electrical stop
0
YES, 1
NO
Bit08
not used
0
NO,
1
YES
Bit11
not used
0
NO,
1
YES
Bit12
Hand Operation
0
NO,
1
YES
Bit13
Motor potentiometer MOP up
0
NO,
1
YES
Bit14
Motor potentiometer MOP down
0
NO,
1
YES
Bit15
Auto Operation
0
NO,
1
YES
Note:
When BICO technology is used to allocate functions to panel buttons, this parameter displays the actual status of the
relevant command.
The following functions can be "connected" to individual buttons:
- ON/OFF1
- JOG
- INCREASE
- OFF2
- REVERSE
- DECREASE
r0020
CO: Act. frequency setpoint
Displays actual frequency setpoint (output from ramp function generator).
Unit: Hz
Min: -
Def: -
Max: -
Level 3
r0021
CO: Act. frequency
Displays actual variable speed drive output frequency (r0024) excluding slip compensation,
resonance damping and frequency limitation.
Unit: Hz
Min: -
Def: -
Max: -
Level 3
r0022
Act. rotor speed
Displays calculated rotor speed based on variable speed drive output frequency [Hz] x 120 /
number of poles.
Unit: 1/min
Min: -
Def: -
Max: -
Level 3
Note:
This calculation makes no allowance for load-dependent slip.
r0024
CO: Act. output frequency
Displays actual output frequency (slip compensation, resonance damping and frequency
limitation are included).
Unit: Hz
Min: -
Def: -
Max: -
Level 3
r0025
CO: Act. output voltage
Displays [rms] voltage applied to motor.
Unit: V
Min: -
Def: -
Max: -
Level 3
r0026[2]
CO: Act. DC-link voltage
Displays DC-link voltage.
Unit: V
Min: -
Def: -
Max: -
Level 3
r0027
CO: Act. output current
Displays [rms] value of motor current [A].
Unit: A
Min: -
Def: -
Max: -
Level 3
r0031
CO: Act. torque
Displays motor torque.
Unit: Nm
Min: -
Def: -
Max: -
Level 3
r0032
CO: Act. power
Displays motor power.
Unit: -
Min: -
Def: -
Max: -
Level 3
Dependency:
Value is displayed in [kW] or [hp] depending on setting for P0100 (operation for Europe / North America).
Содержание SED2 Series
Страница 2: ...2 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products 01 2002 ...
Страница 10: ...10 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Introduction 01 2002 ...
Страница 52: ...52 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Commissioning 01 2002 ...
Страница 125: ...125 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en Landis Staefa Division Index 01 2002 ...