48/126
Siemens Building Technologies
SED2 variable speed drives
CM1U5192en
HVAC Products
Commissioning
01.2002
5.4.3
Motor data for parameterization
50 Hz
230/400V
0.61 0.35 A
Cos j0.81
Cos j0.81
65%
0.12kW
2800 / min
3_Mot
IEC 56
IM B3
Nr. ED510 3053
IP54
Rot KL 16
60 Hz
440V Y
0.34A
0.14 kW
3310 /min
S.F. -- 1.15
12.022
I.CI.F
P0308 P0310
P0304
P0309
P0305 P0311
P0307
5.4.4
Commissioning with the BOP or AOP
5.4.4.1 Country-specific default settings for operation with the BOP
Parameter Description
Default setting for Europe (North America)
P0100
European or US op
mode
0 = 50 Hz, kW
(1 = 60Hz, hp)
(2 = 60Hz, kW)
1,2
.
P0307
Nominal motor power
Value in kW (hp)
Unit depends on the setting in P0100
2
.
P0310
Nominal motor
frequency
50 Hz (60 Hz).
P0311
Nominal motor speed
1395 (1680) U/min (depends on model)
3
.
P1082
Max. motor frequency
50 Hz (60 Hz).
1
Use DIP switch 2 under the BOP/AOP. This overwrites the above parameter settings.
2
This parameter can only be modified if P00010 = 1 (commissioning mode).
3
This parameter can only be modified if P00010 = 1 or 3.
Содержание SED2 Series
Страница 2: ...2 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products 01 2002 ...
Страница 10: ...10 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Introduction 01 2002 ...
Страница 52: ...52 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Commissioning 01 2002 ...
Страница 125: ...125 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en Landis Staefa Division Index 01 2002 ...