18/126
Siemens Building Technologies
SED2 variable speed drives
CM1U5192en
HVAC Products
Mechanical installation
01.2002
3.3.4
Mounting SED2 drives with IP54 / NEMA 12 rating
Hole spacing
Clearance (mm)
Frame size H (mm) W(mm) Top
Botto
m
Side
Mounting materials
Tightening
torque
B
342.8
230
150
150
100
4xM6 bolts
4xM6 washers
4xM6 spring lock washers
5 Nm
C
564
312.7
150
150
100
4xM6 bolts
4xM6 washers
4xM6 spring lock washers
5 Nm
D
647
310
200
200
150
4xM8 bolts
4xM8 washers
4xM8 spring lock washers
13 Nm
E
847
310
200
200
150
4xM8 bolts
4xM8 washers
4xM8 spring lock washers
13 Nm
F
1112
400
300
250
150
4xM8 bolts
4xM8 washers
4xM8 spring lock washers
20 Nm
Drilling plan for SED2
IP54
W
H
5192M02