89/126
Siemens Building Technologies
SED2 variable speed drives
CM1U5192en
HVAC Products
Programming
01.2002
31=MOP se Fixed frequency
32=Analog se Fixed frequency
33=Fixed fre Fixed frequency
34=USS on BOP link + Fixed frequency
35=USS on COM link + Fixed frequency
36=CB on COM link + Fixed frequency
37=Analog setpoint 2 + Fixed frequency
71=MOP se Analog setpoint 2
72=Analog se Analog setpoint 2
73=Fixed fre Analog setpoint 2
74=USS on BOP link + Analog setpoint 2
75=USS on COM link + Analog setpoint 2
76=CB on COM link + Analog setpoint 2
77=Analog setpoint 2 + Analog setpoint 2
Index:
P1000[0] : 1st command data set (CDS)
P1000[1] : 2nd command data set (CDS)
Note:
Single digits denote main setpoints that have no additional setpoint.
P1001
Fixed frequency 1
Defines fixed frequency setpoint 1.
Unit: Hz
Min: -650.0
Def: 0.00
Max: 650.00
Level 3
There are 3 types of fixed frequencies:
1.
Direct selection (P0701 - P0706=15)
In this mode of operation 1 digital input selects 1 fixed frequency. If several inputs are active together, the selected
frequencies are summed, e.g., FF1 + FF2 + FF3 + FF4 + FF5 + FF6.
2. Direct sel ON command (P0701 - P0706=16)
The fixed frequency selection combines the fixed frequencies with an ON command. In this mode of operation 1
digital input selects 1 fixed frequency. If several inputs are active together, the selected frequencies are summed,
e.g., FF1 + FF2 + FF3 + FF4 + FF5 + FF6.
3.
Binary coded sel ON command (P0701 - P0706=17)
Select up to 16 fixed frequencies using this method. Select the fixed frequencies according to the following table:
DIN4
DIN3
DIN2
DIN1
OFF
Inactive
Inactive
Inactive
Inactive
P1001
FF1
Inactive
Inactive
Inactive
Active
P1002
FF2
Inactive
Inactive
Active
Inactive
P1003
FF3
Inactive
Inactive
Active
Active
P1004
FF4
Inactive
Active
Inactive
Inactive
P1005
FF5
Inactive
Active
Inactive
Active
P1006
FF6
Inactive
Active
Active
Inactive
P1007
FF7
Inactive
Active
Active
Active
P1008
FF8
Active
Inactive
Inactive
Inactive
P1009
FF9
Active
Inactive
Inactive
Active
P1010
FF10
Active
Inactive
Active
Inactive
P1011
FF11
Active
Inactive
Active
Active
P1012
FF12
Active
Active
Inactive
Inactive
P1013
FF13
Active
Active
Inactive
Active
P1014
FF14
Active
Active
Active
Active
Data:
P1015
FF15
Active
Active
Active
Active
Dependency:
Select fixed frequency operation (using P1000).
Variable speed drive requires ON command to start in the case of direct selection (P0701 to P0706=15).
Note:
Fixed frequencies can be selected using the digital inputs, and can also be combined with an ON command.
P1002-P1015
Fixed frequency 2 through 15
Defines fixed frequency setpoint 2.
Unit: Hz
Min: -650.00
Def: See Note below
Max: 650.00
Level 3
Details:
See P1001 (fixed frequency 1).
Default fixed frequency setpoint values are as follows:
Fixed Frequency
Default
Fixed Frequency
Default
Fixed Frequency
Default
1
0.00
6
25.00
11
50.00
2
5.00
7
30.00
12
55.00
3
10.00
8
35.00
13
60.00
4
15.00
9
40.00
14
65.00
Note:
5
20.00
10
45.00
15
65.00
P1016 to
P1019
Fixed frequency mode - Bit 0 through 3
Fixed frequencies can be selected in three different modes. Parameter P1016 defines the
mode of selection Bit 0.
Unit: -
Min: 1
Def: 1
Max: 3
Level 3
Details:
Parameter P1016 defines the mode of Bit 0, Parameter P1017 defines the mode of Bit 1, Parameter P1018 defines the
mode of Bit 2, and Parameter P1019 defines the mode of Bit 3.
Settings:
1=Direct selection
2=Direct sel ON command
3=Binary coded sel ON command
Note:
See table in P1001 (fixed frequency 1) for a description of how to use fixed frequencies.
P1020[2] to
P1023[2]
BI: Fixed frequency selection Bit 0
Defines origin of fixed frequency selection.
Unit: -
Min: 0:0
Def: 0:0 (P1023 = 722:3)
Max: 4000:0
Level 3
Settings:
P1020= 722.0 ==> Digital input 1
P1021= 722.1 ==> Digital input 2
P1022= 722.2 ==> Digital input 3
P1023= 722.3 ==> Digital input 4
P1026= 722.4 ==> Digital input 5
P1028= 722.5 ==> Digital input 6
Index:
P1020[0] : 1st command data set (CDS) for Bit 0
P1021[0] : 1st command data set (CDS) for Bit 1
P1022[0] : 1st command data set (CDS) for Bit 2
P1023[0] : 1st command data set (CDS) for Bit 3
P1020[1] : 2nd command data set (CDS) for Bit 0
P1021[1] : 2nd command data set (CDS) for Bit 1
P1022[1] : 2nd command data set (CDS) for Bit 2
P1023[1] : 2nd command data set (CDS) for Bit 3
Содержание SED2 Series
Страница 2: ...2 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products 01 2002 ...
Страница 10: ...10 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Introduction 01 2002 ...
Страница 52: ...52 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Commissioning 01 2002 ...
Страница 125: ...125 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en Landis Staefa Division Index 01 2002 ...