Programming
01.2002
Note:
The PID setpoint source is selected using P2253. The PID setpoint and the PID feedback signal are interpreted as [%]
values (not [Hz]). The output of the PID controller is displayed as [%] and then normalized into [Hz] through P2000
(reference frequency) when PID is enabled. In level 3, the PID controller source enable can also come from the digital
inputs in settings 722.0 to 722.2 for DIN1 to DIN3 or from any other BiCo source.
The minimum and maximum motor frequencies (P1080 and P1082) as well as the skip frequencies (P1091 to P1094)
remain active on the variable speed drive output. However, enabling skip frequencies with PID control can produce
instabilities.
P2201
through
P2215
Fixed PID setpoint 1 through 15
Defines fixed PID setpoint 1
Unit: %
Min: -200.00
Def: See Note Below
Max: 200.00
Level 3
Defines fixed PID setpoint 1. In addition, you can set any of the digital input parameters to fixed PID setpoint via the
digital inputs (P0701 - P0706).
There are three selection modes for the PID fixed setpoint:
1.
Direct selection (P0701=15 or P0702=15, etc)
In this mode of operation, 1 digital input selects one PID fixed setpoint.
2.
Direct selection with ON command (P0701=16 or P0702=16, etc.)
Description as for 1), except that this type of selection issues an ON command concurrent with any setpoint selection.
3.
Binary Coded Decimal selection with ON command (P0701 - P0706=17)
Using this method to select the PID Fixed Setpoint allows you to choose up to 16 different PID setpoints. The
setpoints are selected according to the following table:
DIN4
DIN3
DIN2
DIN1
OFF
Inactive
Inactive
Inactive
Inactive
P2201
FF1
Inactive
Inactive
Inactive
Active
P2202
FF2
Inactive
Inactive
Active
Inactive
P2203
FF3
Inactive
Inactive
Active
Active
P2204
FF4
Inactive
Active
Inactive
Inactive
P2205
FF5
Inactive
Active
Inactive
Active
P2206
FF6
Inactive
Active
Active
Inactive
P2207
FF7
Inactive
Active
Active
Active
P2208
FF8
Active
Inactive
Inactive
Inactive
P2209
FF9
Active
Inactive
Inactive
Active
P2210
FF10
Active
Inactive
Active
Inactive
P2211
FF11
Active
Inactive
Active
Active
P2212
FF12
Active
Active
Inactive
Inactive
P2213
FF13
Active
Active
Inactive
Active
P2214
FF14
Active
Active
Active
Active
Details:
P2215
FF15
Active
Active
Active
Active
Dependency:
P2000=1 required in user access level 2 to enable setpoint source.
In mode 1 (above):
ON command required to start motor (enable pulses).
In mode 2 (above):
If inputs programmed to PID fixed setpoint and selected together, the selected setpoints are summed.
You may mix different types of frequencies; however, remember that they will be summed if selected together.
P2201=100 % corresponds to 4000 hex.
Default fixed PID setpoint values are as follows:
Fixed PID
Default
Fixed PID
Default
Fixed PID
Default
1
0.00
6
50.00
11
100.00
2
10.00
7
60.00
12
110.00
3
20.00
8
70.00
13
120.00
4
30.00
9
80.00
14
130.00
Note:
5
40.00
10
90.00
15
130.00
P2216,
P2217,
P2218, P2219
Fixed PID setpoint mode - Bit 0, Bit 1, Bit 2, and Bit 3
Fixed frequencies for PID setpoint can be selected in three different modes. Parameter P1016
defines the mode of selection bit 0.
Unit: -
Min: 1
Def: 1
Max: 3
Level 3
Settings:
1=Direct selection
2=Direct sel ON command
3=Binary coded sel ON command
P2220[2]
BI: Fixed PID setpoint select Bit 0
Defines command source of fixed PID setpoint selection bit 0.
Unit: -
Min: 0:0
Def: 0:0
Max: 4000:0
Level 3
Settings:
722.0=Digital input 1 (requires P0701 set to 99, BICO)
722.1=Digital input 2 (requires P0702 set to 99, BICO)
722.2=Digital input 3 (requires P0703 set to 99, BICO)
722.3=Digital input 4 (requires P0704 set to 99, BICO)
722.4=Digital input 5 (requires P0705 set to 99, BICO)
722.5=Digital input 6 (requires P0706 set to 99, BICO)
722.6=Digital input 7 (via analog input 1, requires P0707 set to 99)
722.7=Digital input 8 (via analog input 2, requires P0708 set to 99)
Index:
P2220[0] : 1st command data set (CDS)
P2220[1] : 2nd command data set (CDS)
Содержание SED2 Series
Страница 2: ...2 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products 01 2002 ...
Страница 10: ...10 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Introduction 01 2002 ...
Страница 52: ...52 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Commissioning 01 2002 ...
Страница 125: ...125 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en Landis Staefa Division Index 01 2002 ...