SED2 variable speed drives
CM1U5192en
HVAC Products
Programming
01.2002
Unit: -
Min: -
Def: -
Max: -
Bit fields:
Bit00
Fixed frequency Bit 0
0
NO, 1
YES
Bit01
Fixed frequency Bit 1
0
NO, 1
YES
Bit02
Fixed frequency Bit 2
0
NO, 1
YES
Bit03
Fixed frequency Bit 3
0
NO, 1
YES
Bit08
PID enabled
0
NO, 1
YES
Bit09
DC brake enabled
0
NO, 1
YES
Bit11
Droop
0
NO, 1
YES
Bit12
Not Used
0
NO, 1
YES
Bit13
External fault 1
0
YES, 0
NO
r0056
CO/BO: Status of motor control
Displays status of motor control (V/f status), which can be used to diagnose variable speed
drive status.
Unit: -
Min: -
Def: -
Max: -
Level 3
Bit fields:
Bit00
Init. control finished
0
NO, 1
YES
Bit01
Motor demagnetizing finished
0
NO, 1
YES
Bit02
Pulses enabled
0
NO, 1
YES
Bit03
Voltage soft start select
0
NO, 1
YES
Bit04
Motor excitation finished
0
NO, 1
YES
Bit05
Starting boost active
0
NO, 1
YES
Bit06
Acceleration boost active
0
NO, 1
YES
Bit07
Frequency is negative
0
NO, 1
YES
Bit08
Field weakening active
0
NO, 1
YES
Bit09
Volts setpoint limited
0
NO, 1
YES
Bit10
Slip frequency limited
0
NO, 1
YES
Bit11
F_out > F_max
Freq. limited
0
NO, 1
YES
Bit12
Phase reversal selected
0
NO, 1
YES
Bit13
I-max controller active
0
NO, 1
YES
Bit14
Vdc-max controller active
0
NO, 1
YES
Bit15
Vdc-min controller active
0
NO, 1
YES
r0061
CO: Act. rotor speed
Displays current speed detected by encoder.
Unit: Hz
Min: -
Def: -
Max: -
Level 3
r0086
CO: Act. active current
Displays active (real part) of motor current.
Unit: A
Min: -
Def: -
Max: -
Level 3
Dependency:
Applies when V/f control is selected in P1300 (control mode); otherwise, the display shows the value zero.
P0100
Europe / North America
Determines whether power settings (e.g. nominal rating plate power - P0307) are expressed in
[kW] or [hp].
The default settings for the nominal rating plate frequency (P0310) and maximum motor
frequency (P1082) are also set automatically here, in addition to reference frequency (P2000).
Unit: -
Min: 0
Def: 0
Max: 2
Level 1
Settings:
0=Europe [kW], frequency default 50 Hz
1=North America [hp], frequency default 60 Hz
2=North America [kW], frequency default 60 Hz
The setting of DIP switch 2 under the I/O board determines the validity of settings 0 and 1 for P0100 according to the
following table:
DIP 2 Setting
Meaning
P0100 Setting
Meaning
Off
[kW], frequency default 50 [Hz]
Overwrites
1
[hp], frequency default 60 [Hz]
On
[hp], frequency default 60 [Hz]
Overwrites
0
[kW], frequency default 50 [Hz]
Dependency:
Stop drive first (i.e. disable all pulses) before you change this parameter.
P0010=1 (commissioning mode) enables changes to be made.
Changing P0100 resets all rated motor parameters as well as other parameters that depend on the rated motor
parameters (see P0340 - calculation of motor parameters).
Note:
P0100 setting 2 (==> [kW], frequency default 60 [Hz]) is not overwritten by the setting of DIP switch 2 (see table above).
r0200
Act. power stack code number
Identifies hardware variant
Unit: -
Min: -
Def: -
Max: -
Level 3
Note:
Parameter r0200=0 indicates that no power stack has been identified.
r0206
Rated variable speed drive power [kW] / [hp]
Displays nominal rated motor power from the variable speed drive.
Unit: -
Min: -
Def: -
Max: -
Level 3
Dependency:
Value is displayed in [kW] or [hp] depending on setting for P0100 (operation for Europe / North America).
r0207
Rated variable speed drive current
Displays maximum continuous output current of the variable speed drive.
Unit: A
Min: -
Def: -
Max: -
Level 3
r0208
Rated variable speed drive voltage
Displays nominal AC supply voltage of the variable speed drive.
Unit: V
Min: -
Def: -
Max: -
Level 3
Value:
r0208=230 : 200 - 240 V +/- 10 %
r0208=400 : 380 - 480 V +/- 10 %
r0208=575 : 500 - 600 V +/- 10 %
Содержание SED2 Series
Страница 2: ...2 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products 01 2002 ...
Страница 10: ...10 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Introduction 01 2002 ...
Страница 52: ...52 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Commissioning 01 2002 ...
Страница 125: ...125 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en Landis Staefa Division Index 01 2002 ...