SED2 variable speed drives
CM1U5192en
HVAC Products
Programming
01.2002
r0035
CO: Act. motor temperature
Displays measured motor temperature.
Unit: °C
Min: -
Def: -
Max: -
Level 3
r0039
CO: Energy consumption meter [kWh]
Displays electrical energy used by variable speed drive since display was last reset (see
P0040 - reset energy consumption meter).
Unit: kWh
Min: -
Def: -
Max: -
Level 3
Dependency:
Value is reset when P3900=1 (end quick commissioning), P0970=1 (factory reset) or P0040=1 (reset energy
consumption meter).
P0040
Reset energy consumption meter
Resets value of parameter r0039 (energy consumption meter) to zero.
Unit: -
Min: 0
Def: 0
Max: 1
Level 3
Settings:
0=No reset
1=Reset r0039 to 0.
Dependency:
No reset until "P" is pressed.
r0052
CO/BO: Act. status word 1
Displays first active status word of variable speed drive (bit format) and can be used to
diagnose variable speed drive status.
Unit: -
Min: -
Def: -
Max: -
Level 3
Bit fields:
Bit00 Drive ready
0
NO,
1
YES
Bit01 Drive ready to run
0
NO,
1
YES
Bit02 Drive running
0
NO,
1
YES
Bit03 Drive fault active
0
NO,
1
YES
Bit04 OFF2 active
0
YES, 1
NO
Bit05 OFF3 active
0
YES, 1
NO
Bit06 ON inhibit active
0
NO,
1
YES
Bit07 Drive warning active
0
NO,
1
YES
Bit08 Deviation setp/act value
0
YES, 1
NO
Bit09 PZD control
0
NO,
1
YES
Bit10 Maximum frequency reached
0
NO,
1
YES
Bit11 Warning: Motor current limit
0
YES, 1
NO
Bit12 Motor holding brake active
0
NO,
1
YES
Bit13 Motor overload
0
YES, 1
NO
Bit14 Motor runs direction right
0
NO,
1
YES
Bit15 VSD drive overload
0
YES, 1
NO
Note:
Output of Bit3 (Fault) will be inverted on digital output high=No Fault).
r0053
CO/BO: Act. status word 2
Displays second status word of variable speed drive (in bit format).
Unit: -
Min: -
Def: -
Max: -
Level 3
Bit fields:
Bit00
DC brake active
0
NO, 1
YES
Bit01
Act. freq. r0024
>
P2167
0
NO, 1
YES
Bit02
Act. freq. r0024
>
P1080
0
NO, 1
YES
Bit03
Act. current r0027 >= P2170
0
NO, 1
YES
Bit04
Act. freq. r0024
>
P2155
0
NO, 1
YES
Bit05
Act. freq. r0024
<= P2155
0
NO, 1
YES
Bit06
Act. freq. r0024 >= setpoint
0
NO, 1
YES
Bit07
Act. Vdc r0026 <
P2172
0
NO, 1
YES
Bit08
Act. Vdc r0026 >
P2172
0
NO, 1
YES
Bit09
Ramping finished
0
NO, 1
YES
Bit10
PID output r2294
<
P2291
0
NO, 1
YES
Bit11
PID output r2294
>= P2291
0
NO, 1
YES
Bit14
Download data set 0 from AOP
0
NO, 1
YES
Bit15
Download data set 1 from AOP
0
NO, 1
YES
r0054
CO/BO: Act. control word 1
Displays first control word of variable speed drive and can be used to diagnose which
commands are active.
Unit: -
Min: -
Def: -
Max: -
Level 3
Bit fields:
Bit00
ON/OFF1
0
NO, 1
YES
Bit01
OFF2: Electrical stop
0
YES, 1
NO
Bit02
OFF3: Fast stop
0
YES, 1
NO
Bit03
Pulse enable
0
NO, 1
YES
Bit04
RFG enable
0
NO, 1
YES
Bit05
RFG start
0
NO, 1
YES
Bit06
Setpoint enable
0
NO, 1
YES
Bit07
Fault acknowledge
0
NO, 1
YES
Bit08
JOG right
0
NO, 1
YES
Bit09
JOG left
0
NO, 1
YES
Bit10
Control from PLC
0
NO, 1
YES
Bit11
Reverse (setpoint inversion)
0
NO, 1
YES
Bit13
Motor potentiometer MOP up
0
NO, 1
YES
Bit14
Motor potentiometer MOP down
0
NO, 1
YES
Bit15
CDS Bit 0 (Local/Remote-Hand/Auto) 0
NO, 1
YES
r 0055
CO/BO: Add. act. control word
Displays additional control word of variable speed drive and can be used to diagnose which
commands are active.
Level 3
Содержание SED2 Series
Страница 2: ...2 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products 01 2002 ...
Страница 10: ...10 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Introduction 01 2002 ...
Страница 52: ...52 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Commissioning 01 2002 ...
Страница 125: ...125 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en Landis Staefa Division Index 01 2002 ...