Programming
01.2002
r0774
Shows the analog output value (in V or mA) after filtering and scaling.
Index:
P0774[0]: Analog output 1 (DAC 1).
P0774[1]: Analog output 2 (DAC 2).
P0776
Defines the type of analog output.
Possible settings:
0
Current output
0 to 20 mA (factory setting)
1
Voltage output
0 to 10 V
Note:
The analog outputs are designed as current outputs within 0 to 20 mA. Both
analog outputs must be configured as the same type. Both channels are
configured, e.g., as either current outputs with range 0 to 20 mA, or as voltage
outputs with range 0 to 10 V.
P0777 to P0780:
Define the output characteristic in %. The DAC scaling parameters (P0777 to P0781)
are used to set the output characteristics. They are configured according to the
following curve.
Ausgangssignal (mA)
0
20
20 mA
P0780 y2
P0778 y1
P0777
x1
P0779
x2
100%
(-100%)
Points P1 (x1, y1) and P2 (x2, y2) are freely selectable.
Example:
The factory-set scaling is as follows:
P1:
0.0 % = 0 mA or 0 V and
P2: 100.0 % = 20 mA or 10 V.
Index:
P0777[0]: Analog output 1 (DAC 1).
P0777[1]: Analog output 2 (DAC 2).
P0777:
Defines x1 of the output characteristics (factory setting = 0.0).
P0778:
Defines y1 of the output characteristics (factory setting = 0).
P0779:
Defines x2 of the output characteristics (factory setting = 100).
P0780:
Defines y1 of the output characteristics (factory setting = 10).
Содержание SED2 Series
Страница 2: ...2 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products 01 2002 ...
Страница 10: ...10 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Introduction 01 2002 ...
Страница 52: ...52 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Commissioning 01 2002 ...
Страница 125: ...125 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en Landis Staefa Division Index 01 2002 ...