49/126
Siemens Building Technologies
SED2 variable speed drives
CM1U5192en
HVAC Products
Commissioning
01.2002
5.4.4.2
Setting parameters with the BOP or AOP
The following describes how to change parameter P1082. Use this description as a
guide to setting all other parameters with the BOP.
Step
Action
Resulting display
1
Press
to access the parameters.
2
Press
until P0004 is displayed.
3
Press
to access the parameter value level.
4
Press
or
to display the required value.
5
Press
to confirm and save the value.
6
Only the motor parameters are now visible for the user.
Step
Action
Resulting display
1
Press
to access the parameters.
2
Press
until P1082 is displayed.
3
Press
to access the parameter value level.
4
Press
or
to display the required value.
5
Press
to confirm and save the value.
6
Press
to return to P0010.
Hz
P(1)
P0010
7
Press
to access the parameter value level P0010.
Hz
P(1)
1
8
Press
to restore the value to P0010 = 0.
Hz
P(1)
0
9
Press
to save the parameter and exit the parameter value
level.
Hz
P(1)
P0010
10
Press
until r0000 is displayed.
11
Press
to revert to the standard motor display (as defined
by the customer).
Changing P0004 –
parameter filter function
Changing an indexed
value under P1082 –
setting the maximum
motor frequency
Содержание SED2 Series
Страница 2: ...2 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products 01 2002 ...
Страница 10: ...10 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Introduction 01 2002 ...
Страница 52: ...52 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Commissioning 01 2002 ...
Страница 125: ...125 126 Siemens Building Technologies SED2 variable speed drives CM1U5192en Landis Staefa Division Index 01 2002 ...