81/118
Siemens
Heating and D.h.w. Controller RVL481
CE1P2541en
Building Technologies
24 Function block "Switching program 3"
20.05.2008
24 Function
block
"Switching program 3"
Switching program 3 of this function block can be used for one or several of the follow-
ing functions:
•
As a time switch program for the circulating pump (operating line 122)
•
As a time switch program for the multifunctional relay (operating lines 141 and 146)
24.1 Operating
lines
Line Function, parameter
Factory setting (range)
Unit
151
Weekday for switching program 3
1-7 (1…7, 1-7)
152
Start of first ON period
06:00 (--:-- / 00:00…24:00)
hh:mm
153
End of first ON period
22:00 (--:-- / 00:00…24:00)
hh:mm
154
Start of second ON period
--:-- (--:-- / 00:00…24:00)
hh:mm
155
End of second ON period
--:-- (--:-- / 00:00…24:00)
hh:mm
156
Start of third ON period
--:-- (--:-- / 00:00…24:00)
hh:mm
157
End of third ON period
--:-- (--:-- / 00:00…24:00)
hh:mm
24.2 Function
Switching program 3 of the RVL481 affords a maximum of 3 ON periods per day. Also,
every day of week may have different ON periods.
As with the heating program, it is not switching times that are entered, but periods of
time during which the program or the controlled function shall be active.
Using the setting "1-7" on operating line 151, it is possible to enter a heating program
that applies to all days of the week. This simplifies the settings: If the weekend times
differ, enter the times for the entire week first, and then change days 6 and 7 as re-
quired.
The entries are sorted and overlapping ON periods combined.