85/118
Siemens
Heating and D.h.w. Controller RVL481
CE1P2541en
Building Technologies
25 Function block "Service functions and general settings"
20.05.2008
There are 4 choices to terminate the relay test:
•
Entry of 0 on the operating line
•
Leaving the setting level by pressing button
or
•
Leaving the setting level by pressing the Info button or any of the operating mode
buttons
•
Automatically after 30 minutes
25.3.3 Sensor
test
The connected sensors can be checked on operating line 163. In addition, if available,
the current setpoints and limit values are displayed.
On the display, the current setpoints are identified by SET, the actual values by
ACTUAL (also refer to chapter “29 Handling”)
The 9 temperatures can be called up by entering 0…8:
Input
Display SET
Display ACTUAL
0
No display
Actual value of outside sensor at
terminal B9.
If the outside temperature is
delivered via the data bus, the
display shows ---
1
Setpoint of flow / boiler temperature.
With the plant types using a boiler, the
switch-off point is displayed. If there is
no demand for heat, the display
shows ---
Actual value of flow / boiler tem-
perature sensor at terminal B1
2
Setpoint of room temperature.
With the plant types with no heating
circuit, the display shows ---
Actual value of room temperature
sensor at terminal B5
3
Setpoint of room temperature.
With the plant types with no rooms, the
display shows ---
Actual value of room unit sensor
at terminal A6
4
Limit value of return temperature.
With plant types 1–x, 4–x, and 5–x, the
minimum limit value of the return tem-
perature is displayed; with plant types
3–x and 6–x, the maximum limit value of
the return temperature.
If no return temperature limitation is
used, the display shows ---
Actual value of return tempera-
ture sensor at terminal B7.
If the return temperature is deliv-
ered via data bus, the display
shows ---
5
Limit value of return temperature differ-
ential.
If no DRT limitation is used, the display
shows ---
Actual value of the secondary
return temperature sensor at
terminal B71
6
Setpoint of d.h.w. flow temperature.
With plant types with no d.h.w. flow, the
display shows ---
Actual value of the d.h.w. flow
temperature sensor at terminal
B3
7
Setpoint of d.h.w. temperature.
With plant types with no storage tank,
the display shows ---
Actual value of the storage tank
temperature sensor / thermostat
at terminal B31
8
Setpoint of d.h.w. temperature.
With plant types with no storage tank,
the display shows ---
Actual value of the storage tank
temperature sensor / thermostat
at terminal B32
9
Actual value storage tank temperature
B32
Actual value of the temperature
at the collector, terminal B6
Faults in the measuring circuits are displayed as follows:
= short-circuit (thermostat: contact closed)
= open-circuit (thermostat: contact open)