17 Function block "Release of d.h.w. heating"
20.05.2008
17.2.2 Release
programs
Depending on the setting made on operating line 123, release of d.h.w. heating takes
place at the following times:
Setting
D.h.w. heating is released
0
Continuously (24 hours a day)
1
According to one or several heating programs
2
According to switching program 2 of own controller
With setting 1, d.h.w release depends on the setting made on operating line 121. In an
interconnected system of several controllers, that is, in the case of several heating
programs, the circulating pump runs if at least one of the connected controllers pro-
vides heating to the NORMAL temperature according to its heating program (independ-
ent of the operating mode), and is not in holiday mode.
Release of d.h.w. heating is shifted forward in time by one hour against the times of the
heating program. If optimum start control is active, the optimized switch-on times are
used – and not the times entered.
With plant types 4–x, 5–x, and 6–x, and the setting of 0 (own controller) on operating
line 121, d.h.w. heating will never be released since these plant types have no own
heating program.
The release of d.h.w. heating is explained using 2 examples, in which controllers A, B,
C and D are interconnected via the data bus:
Operating line
121 123
Con-
trollers
Operating
mode
Heating program, optimi-
zation, holidays
Release
A
06:00…18:00,
no optimization
B
07:00…23:00
C
07:00…22:00, optimum
start control shifts forward
by 2 hours
2 1
D
03:00…22:00, HOLIDAYS
D.h.w. heating
is released from
04:00 to 23:00
Operating line
121 123
Con-
trollers
Operating
mode
Heating program, optimi-
zation, holidays
Release
A
06:00…18:00,
no optimization
B
08:00…23:00
C
07:00…22:00, optimum
start control shifts forward
by 2 hours
2
1
D
05:00…21:00
D.h.w. heating
is released
from 04:00 to
23:00
17.2.3 D.h.w heating during the holiday period
In holiday mode, d.h.w. heating is provided as follows:
Operating
line 121
Operating
line 123
D.h.w. heating
0
0, 1, or 2
No d.h.w. heating when own controller is in
holiday mode
1
0, 1, or 2
No d.h.w. heating when all controllers in the
same segment are in holiday mode
2
0, 1, or 2
No d.h.w. heating when all controllers in the
interconnected system are in holiday mode
Example 1
Example 2