23 Function block "Legionella function"
20.05.2008
23.2 Mode of operation
Preconditions for the legionella function:
•
The d.h.w. storage tank temperature is acquired with one or 2 sensors (the legionella
function is not possible with thermostats)
•
Charging takes place instantaneously with the heating water and not with the electric
immersion heater
•
A legionella setpoint is adjusted
•
D.h.w. heating is switched on (button
lit)
•
The holiday function and operating mode changeover via contact H1 are not active
When the periodicity and time criteria are satisfied, the legionella function will be re-
leased. Release of the legionella function means that the d.h.w. temperature setpoint
will be raised to the legionella setpoint and forced charging is enabled. If d.h.w. heating
is switched off or the holiday function or operating mode changeover active, the le-
gionella function will be released, but not the setpoint boost. On termination of the over-
riding function, d.h.w. heating to the legionella setpoint will again be triggered since the
legionella function is still released.
The behavior of the legionella function as a function of the d.h.w. temperature is as
follows:
T
BWw
T
BWw
- SD
BW
T
BWw
- SD
BW
- 2 K
T
BWx
T
BWx
t
2541
D
0
4
ON
OFF
ON
OFF
ON
OFF
2541
D
0
4
Start timer
dwelling time
Reset timer
dwelling time
Start timer
dwelling time
Timer dwelling
time elapsed
Circulating pump
Forced charging
Release of
legionella function
Start condition for legionella function satisfied
TBWx D.h.w.
temperature
TBWw
D.h.w temperature setpoint
SDBW
Switching differential of d.h.w. charging
t
Time
If a maximum d.h.w. charging time is set, it also acts here. If the legionella setpoint is
not reached, the legionella function is interrupted and resumed at the end of the maxi-
mum charging time.