21 Function block "Derivative action time d.h.w. heating via heat exchanger"
20.05.2008
21
Function block "Derivative action time
d.h.w. heating via heat exchanger"
With plant types x–4, this function block permits entry of the D-part with d.h.w. control.
21.1 Operating
line
Line Function, parameter
Factory setting (range)
Unit
137
Derivative action time of control (Tv)
16 (0…255)
s
21.2 Description
The 3-position controller provides PID mode. The derivative action time Tv (D-part) can
be set on operating line 137.
A deviation of the flow temperature from the setpoint is offset by incremental adjust-
ment of the 2-port valve. The ideal runtime of the actuator is 10…35 seconds.
In the case of d.h.w. heating via heat exchanger, it is best to set operating lines
133…137 as follows:
Operating line
Parameter
Setting value
133
Actuator opening time
35 s
134
Actuator closing time
35 s
135
P-band of control (Xp)
35 °C
136
Integral action time of control (Tn)
35 s
137
Derivative action time of control (Tv)
16 s