34/118
Siemens
Heating and D.h.w. Controller RVL481
CE1P2541en
Building Technologies
8 Function block "Plant type"
20.05.2008
8
Function block "Plant type"
This function block only contains the selection of the plant type.
8.1 Operating
line
Line Function, parameter
Factory setting (range)
Unit
51 Plant
type
1
−
1 (1
−
0…6
−
5)
8.2 General
When commissioning the plant, the respective plant type must be entered first. This
ensures that the functions required for the specific type of plant, the parameters and
operating lines for the settings and displays will be activated.
All plant-specific variables and operating lines existing for the other plant types will then
be hidden. They will not be displayed.
Example for an entry (selection of plant type 1–2)
25
4
0
Z
0
2
51
1
2
= operating line
= Heating circuit plant type 1
= d.h.w. circuit type 2