4 Acquisition of measured values
20.05.2008
4.4.2 Handling
faults
If there is a short-circuit or open-circuit in the measuring circuit, and if the controller
requires the return temperature, it responds as follows:
•
If there is a return temperature from a controller of the same segment available on the
data bus, it is used (only with plant type 1–x). No error message will be generated
since this is the normal state in interconnected plants
•
However, if there is no return temperature available on the data bus, the return tem-
perature limitation functions will be deactivated and an error message generated
4.5
Secondary return temperature (B71)
4.5.1 Measurement
The secondary return temperature is acquired with a sensor having a sensing element
LG-Ni 1000. This measured value is required for DRT limitation (plant types 3–x and
6–x), together with the primary return temperature.
4.5.2 Handling
faults
If there is a short-circuit or open-circuit in the measuring circuit, and if the controller
requires the return temperature, DRT limitation will be deactivated. An error message
will be generated
4.6
D.h.w. flow temperature (B3)
4.6.1 Measurement
The d.h.w. flow temperature is acquired with a sensor having a sensing element
LG-Ni 1000.
4.6.2 Handling
faults
If there is a short-circuit or open-circuit in the measuring circuit, the d.h.w. will no longer
be heated. The charging pump is deactivated and the actuating device (slipper or seat
valve) is shut.
An error message will be generated.
4.7
D.h.w. storage tank temperature (B31, B32)
4.7.1 Measurement
The storage tank temperature can be acquired as follows:
•
With one or 2 sensors having a sensing element LG-Ni 1000, or
•
With one or 2 thermostats
This means that there are 2 measuring circuits.