89/184
Siemens Building Technologies
Basic Dokumentation RVA63.280, RVA53.280
CE1P2374E
Landis & Staefa Division
19.04.2001
2.28
Minimum limitation of flow temperature
setpoint (TVmin)
Prevents too low flow temperatures.
Minimum and maximum limitation define the range within which the flow temperature
setpoint may vary.
Setting range
Unit
Factory setting
8...TVmax
°C
8
TVmax Maximum limitation of flow temperature setpoint (setting on line 107)
The setting will make certain that the flow temperature setpoint will not fall below a
minimum level.
0
10
20
30
40
50
60
70
80
90
100
TV
max
min
akt
°C
2373
Z
1
5
TVw
TVw
Current flow temperature setpoint
65
Minimum limitation of flow temperature setpoint
70
Maximum limitation of flow temperature setpoint
If the flow temperature setpoint demanded by the heating circuit reaches the minimum
limit and the outside temperature rises, the flow temperature setpoint will be maintained
at that limit, in other words, it will not be allowed to fall below it.
Benefit
Description
Setting
Effect
Limitation