73/184
Siemens Building Technologies
Basic Dokumentation RVA63.280, RVA53.280
CE1P2374E
Landis & Staefa Division
19.04.2001
2.12
Outside temperature source
Display and location of actual outside temperature measurement.
When interconnecting several controllers, only one outside sensor is required. It can be
connected to any of the controllers to deliver its signal via the bus system.
The controllers to which no sensor is connected adopt the outside temperature signal
via the bus system, from a controller to which a sensor is connected.
Display
Unit
– – . – –
00.01...14.16
No signal
Segment and device address
The address of the outside sensor that currently delivers the outside temperature signal
will automatically be displayed on this line.
– – . – –
No outside sensor signal
01.02
Address of outside sensor
The first 2 digits represent the segment number (01.)
The second 2 digits represent the device number (.02)
Benefit
Description
Setting
Effect
Display