112/184
Siemens Building Technologies
Basic Dokumentation RVA63.280, RVA53.280
CE1P2374E
Landis & Staefa Division
19.04.2001
LPB / system
Creation of systems.
Wide field of use with a smaller number of unit versions.
Plants can be extended in a straightforward manner.
2.44
LPB device address
The device address and the segment address are used as destinations in the bus
system. To ensure communication, each device must be correctly addressed.
Setting range
Unit
Factory setting
0...16
Increment
0
Entry of the device address is especially important when using combinations of units, or
in a system. The addresses classify the controllers within a segment.
Address
Effect
Example
0
Standalone
Single controllers
1
Master (LPB)
Controllers with master function
−
Heat generation master
−
Consumer master in the respective
segment
2...16
Slave (LPB)
Controllers with slave functions
−
Zone controller (slave)
The device addresses should be assigned in consecutive order in accordance with the
controllers connected. It is not permitted to assign an address several times within a
bus segment, since this would lead to communication errors. Each segment must have
a device as a master (address 1).
Addressing is part of engineering. For detailed information, refer to LPB System
Engineering, Basic Documentation (reference number CE1P2370E).
Benefits
Description
Setting
Effect
Device address
Note