121/184
Siemens Building Technologies
Basic Dokumentation RVA63.280, RVA53.280
CE1P2374E
Landis & Staefa Division
19.04.2001
2.54
Display of PPS communication
Checking the communication with the connected room unit.
The display provides information about the communication status and the type of room
unit connected.
Prerequisite
is that signal transmission is correct. Also refer to "input
A…" in Index.
Display
Unit
- - -
No communication
0...255
Device identification
0 0 0
Communication line with a short-circuit
The status of PPS communication will automatically be displayed on this line. If
communication is error-free, the controller identifies the unit connected by displaying
the identification number.
The identification of the connected unit is displayed. The list below shows the various
digits with the associated types of units
Only digital peripheral devices can be connected to the controller.
82
Digital room unit QAA50
83
Digital room unit QAA70
90
Digital room sensor QAA10
102
BMU (only with A6)
237
4Z18
a)
b)
a)
Device identification (see list)
b)
Selected setting line
•
As soon as a device identification appears (digit), the communication is error-free
•
If the digit displayed is not one of those listed above, the connected room unit is
incompatible
Within the PPS, a fixed address is assigned to some types of devices:
Room unit
1
BMU
4 (only with A6)
These peripheral devices can only be operated under the respective PPS address.
When connecting a room unit type QAA10, the right polarity of the terminals must be
observed.
Benefit
Description
Setting
Effect
Displays
Identification codes
Example
Notes
PPS-address
Important