Check if d.h.w. heating is released
•
Check wiring and fuse of the charging pump (input test)
•
Check wiring of the d.h.w. temperature sensor (output test)
2.8.1.8
The room temperature does not agree with the required temperature
level:
•
Check the room temperature setpoints
•
Is the required operating mode indicated?
•
Is automatic operation overridden by the room unit?
•
Are weekday, time of day and the displayed heating program correct?
•
Has the heating curve slope been correctly set?
•
Check wiring of outside sensor
2.8.1.9
Heating plant does not function properly
•
Check all parameters based on the setting instructions "Heating engineer" and the
operating instructions "End-user". especially the preselection of the double function
•
Make the input test
•
Make the output test
•
Check the electromechanical control thermostat (TR) and the manual reset safety
limit thermostat (STB)
2.8.1.10
Frost protection for the plant does not function at all, or does not
function correctly
•
Check correct functioning of the burner
•
Check correct functioning of the pumps
•
Frost protection for the plant in the case of pump heating circuits with active room
temperature limitation
2.8.1.11
Quick setback or boost heating does not function
•
Check settings made on the heating engineer's level
•
Fühler an A6,A7 kontrollieren (Eingangtest).
•
Check the sensor connected to A6, A7 (input test)
2.8.1.12
Fault status signal; display shows "ER"
•
For cause of error, refer to section "Parameter settings for end-user" on line 50