Siemens Building Technologies
Basic Dokumentation RVA63.280, RVA53.280
CE1P2374E
Landis & Staefa Division
19.04.2001
2.32
Type of building construction
The building's thermal dynamics are taken into consideration.
The type of building construction affects the control. By considering the type of
construction, a disturbance variable (z) within the controlled system is taken into
account.
Setting range
Unit
Factory setting
0 / 1
Increment
1
When the outside temperature varies, the room temperature changes at different rates,
depending on the building's thermal storage capacity.
The above setting ensures that the generation of the composite outside temperature
will be matched to the type of building construction. Also refer to "Composite outside
temperature“ in section "Functions without settings".
Entry:
0:
Heavy building structures: The room temperature will respond slower to outside
temperature variations
1:
Light building structures: The room temperature will respond quicker to outside
temperature variations
Heavy building structures:
Buildings with thick walls or with external insulation
Light building structures:
Buildings with a light envelope
Benefit
Description
Setting
Effect
Building construction