135/184
Siemens Building Technologies
Basic Dokumentation RVA63.280, RVA53.280
CE1P2374E
Landis & Staefa Division
19.04.2001
3.6
Reset integral of burner stage 2
Optimum switching off of burner stage 2.
Adjustment of the amount of surplus heat for locking burner stage 2.
Setting range
Unit
Factory setting
0...500
°C (K) min
10
The setting will change the switch-off behaviour of burner stage 2.
Entry:
Increase:
Burner stage 2 will be locked when surplus heat is greater
Decrease:
Burner stage 2 will be locked when surplus heat is smaller
If, with burner stages 1 and 2, the switch-off setpoint (TKw + SDK/2) is exceeded by the
amount of the reset integral set here, the controller will lock burner stage 2.
When burner stage 2 is locked, the controller will activate and deactivate burner stage 1
according to the set switching differential.
3.6.1
Temperature-time integral
The temperature-time integral is a continuous summation of the temperature differential
over time. In this case, the decisive criterion is the difference by which the boiler
temperature exceeds the burner’s switch-off setpoint TKx- (TKw+SDK/2).
Through the generation of the temperature-time integral it is not only the period of time
that is considered, but also the extent of overshoot. This means that when the crossing
is significant, burner stage 2 will be locked earlier.
When the release integral (area "b" in the diagram below) has reached the value set
(point in time tR), burner stage 2 will be locked.
50
48
52
TKx
23
7
1
Z
3
4
°C
44
46
t
TKw+SDK/2
TKw
TKw-SDK/2
tR
b
b
reset limit
TKw
Boiler temperature setpoint
TKx
Actual value of boiler temperature
SDK
Switching differential of boiler
t
Time
tR
Time to reset
Benefit
Description
Setting
Effect
Burner stage 2
Note
Switching point
Example