3.12
Gain factor of room influence (KORR)
The influence of room temperature deviations on the controlled system can be
adjusted.
Room influence can be activated and deactivated (setting on line 101).
Setting range
Unit
Factory setting
0...20
-
4
This setting will change the authority of the room temperature influence.
Increase:
Authority of room influence will increase
Decrease:
Authority of room influence will decrease
One half of the setting made on line 31
OEM
is multiplied by the deviation of the room
temperature setpoint from the actual value.
The result is then added to the room temperature setpoint.
TRx)
-
(TRw
2
31
+
TRw
=
TRwk
OEM
TRw
Room temperature setpoint
TRx
Actual value of the room temperature
TRwk
Corrected room temperature setpoint
The gain factor of room influence is only active when a room unit is connected.
Benefit
Note
Setting
Effect
Correction
Note