3.22
P-band mixing valve (Xp)
Adapting the control characteristic to the plant’s behavior (controlled system).
Setting the proportional band for control of mixing valve actuators Y1 and Y5 that can
be used for heating circuit 1 and heating circuit 2.
Setting range
Unit
Factory setting
1...100
°C (K)
32
Xp influences the controller’s P-behavior.
3.23
Integral action time mixing valve (Tn)
Adapting the control characteristic to the plant’s behavior (controlled system).
Setting the I-part for control of mixing valve actuators Y1 and Y5 that can be used for
heating circuit 1 and heating circuit 2.
Setting range
Unit
Factory setting
10...873
s
120
Tn influences the controller’s I-behavior.
3.24
Actuator running time mixing valve
Setting the actuator running time.
Mixing valves have different actuator running times.
Setting range
Unit
Factory setting
30...873
s
120