78/184
Siemens Building Technologies
Basic Dokumentation RVA63.280, RVA53.280
CE1P2374E
Landis & Staefa Division
19.04.2001
2.18
Display of flow temperature setpoint (TVw)
Displays the current flow temperature setpoint of the heating circuit.
When selecting this operating line, the current flow temperature setpoint of the
controller’s internal heating circuit is displayed.
Display
Unit
0...140
°C
The value displayed corresponds to the flow temperature of the heating circuit that is
required for satisfying the demand for heat.
The display shows “---“ in the following situations:
−
No heating circuit available
−
ECO function active (summer / winter changeover, automatic 24-hour heating limit)
−
Quick setback active
−
Room temperature limitation active
Benefit
Description
Setting
Note