34/184
Siemens Building Technologies
Basic Dokumentation RVA63.280, RVA53.280
CE1P2374E
Landis & Staefa Division
19.04.2001
2.8
Operational faults
2.8.1.1
No display on the controller:
•
Is the heating plant's main switch turned on?
•
Are the fuses in order?
•
Check wiring
2.8.1.2
Heating control does not function. There is no display of the time of
day, or the time displayed is incorrect
•
Check fuses of the plant
•
Make a reset: Isolate controller from the mains supply for about 5 seconds (e.g. turn
off the boiler's main switch for 5 seconds)
•
Set the correct time of day on the controller (operating line 1).
•
Check the time of day on the clock time master if the controller is used in a system
2.8.1.3
Controlling element does not open / close or does not operate
correctly.
•
Manual lever of controlling element may not be engaged
•
Wiring to the controlling element interrupted (output test)
•
Check wiring of the sensors (input test)
•
Quick setback or automatic 24-hour heating limit is active
•
Check the settings, especially the selection of the double function
2.8.1.4
Heating circuit pump does not run
•
Is the right type of plant displayed (setting line 53)?
•
Check wiring and fuse (output test)
•
Check wiring of the sensors (input test)
•
Check the settings, especially the selection of the double function
2.8.1.5
Burner does not switch on
•
Press burner's reset button
•
Check the fuses
•
Wiring to the controlling element interrupted (output test)
•
Check the electromechanical control thermostat (TR) and the manual reset safety
limit thermostat (STB)
•
Quick setback or automatic 24-hour heating limit is active
•
Check wiring of the boiler temperature sensor (input test)
2.8.1.6
Pump does not run
•
Check wiring and fuse (output test)
•
Check wiring of the sensors (input test)
2.8.1.7
D.h.w. is not being heated
•
Has the button for d.h.w. heating been activated?
•
Check setting of the electromechanical control thermostat (TR) installed on the
boiler. It must be above the TKmax setting
•
Check setpoint of the d.h.w. temperature
•
Check actual value of the d.h.w. temperature