Central control unit RMB795B
CE1P3122en
Building Technologies
Function block: "Room group"
18.01.2012
8.11 Smoke extraction
Function block "Room group" can be switched to "Smoke extraction" mode via 1 or
2 digital signals at its inputs "SA" and "EA".
8.11.1 Activate function
The function is activated by configuring at least 1 digital input Xx:
Main menu > Commissioning > Extra configuration > Room group 1…10 > Fire and smoke
extraction >
Operating line
Adjustable values / remarks
Smoke extraction
supply air
---, X1, X2, ... (digital inputs only).
Smoke extraction
extract air
---, X1, X2, ... (digital inputs only).
8.11.2 Operating principle
When individual room controllers are used on applications that support the
"Emergency override" function, the RMB795B central control unit can transmit to
them via bus the smoke extraction signal for supply air, extract air or supply air /
extract air operation.
The signal acts on the geographical zone of the relevant room group. It has no
impact on the operating mode of that room group.
For detailed information about the RXB/RXL room controllers that support the
"Emergency override" function, refer to the relevant RXB/RXL documentation.
Smoke extraction with supply air and / or extract air can be configured separately:
•
If smoke extraction is accomplished with supply air and extract air, both function
block inputs can be controlled.
•
Digital input Xx can be configured to smoke extraction with supply air as well as
smoke extraction with extract air.
Smoke extraction has a higher priority than fire alarm off, i.e. extraction is executed
despite the signal "Fire alarm off".
Function
Configuration
Bus telegram to the
individual room
controllers
Notes on configuration
Priority