Central control unit RMB795B
CE1P3122en
Building Technologies
Appendix
18.01.2012
faults
Configuration
Function
Faults
•
Fault inputs 1 through 10
•
Fault relays 1 and 2 (relays...)
•
10 universal fault signal inputs, fault signal delay, fault
acknowledgement (none, acknowledge, acknowledgement and
reset), fault priority (urgent, not urgent) and fault effect (stop, no stop)
can be set.
•
Supervision of analog signals with regard to limit value crossings
•
2 fault status relays, priority (urgent, non-urgent, all) and source
(internal, bus) can be selected
Trend
Configuration
Function
•
Input
The trend is used to log the progression of signals.
•
4 independent trend channels.
•
Logging of local inputs, room temperatures and outside temperature
from the bus.
•
Simultaneous display of 2 channels.
•
Views: 8-minutes, 8-hours, 24-hours and 6-day history.
Meters
Configuration
Function
•
Input
•
Acquisition of pulse sources and display of cumulated values;
selectable unit, valency, presentation, etc.
Logic functions.
Configuration
Function
1 2
2
1
A
B
3
C
•
Input
•
Logic
function
•
Operation
selector
•
Relay
output
•
Digital
output
•
10 logic blocks, logic 1 to 10.
•
Generation of digital signal from continuous input signals.
•
Selectable logic for logic A, B and C.
•
Selectable operation selector.
•
Delay times can be set for output signal.
•
Selectable time formats.
Heat demand
refrigeration demand
Configuration
Function
Q
Y
Relay
Heat demand
•
Forwarding heat demand via
KNX bus
•
Heat demand relay (relay Q)
•
Heat demand modulating
Plant functions when there is demand for heat.
•
Heat demand can also be transmitted via bus, (see Communication).
•
Heat demand relay for passing on the heat demand
•
Heat demand modulating for passing on the heat demand by means
of analog DC 0…10 V signal.
Q
Y
Q
Y
Relay
Refrigeration demand
•
Forwarding refrigeration demand
via KNX bus
•
Refrigeration
demand
relay
(relay Q)
•
Refrig demand modulating
Plant functions when refrigeration is requested.
•
Refrigeration demand can also be transmitted via bus, (see
Communication).
•
Refrigeration demand relay for passing on the refrigeration demand.
•
Refrigeration demand modulating for passing on the heat demand by
means of analog DC 0…10 V signal.