Distribution zones
18.01.2012
11.3.4 Communication
Heat demand can be transmitted over the bus to other devices of a heat
distribution zone on the generation side if communication is activated (see
Sec. 13).
A "Heat distribution zone source side" must be defined, see Sec. 13.2.3
"Distribution zones" menu item".
Main menu > Commissioning > Communication > Distribution zones >
Operating line
Range
Factory setting
Heat distr zone source
side
----, 1…31
----
11.3.5 Functional check / wiring test
For making a functional check during the wiring test, the outputs of the "Heat
demand" function block can be switched directly.
Main menu > Commissioning > Wiring test > Outputs
Operating line
Comments
Heat demand relay
---, 0...100 % (relay switches >= 1 %).
Heat demand modulating
---, 0...100 %
11.4 Function "Refrigeration request"
11.4.1 Purpose and activation
The "Refrigeration request" function collects refrigeration requests from different
devices on the bus.
From these signals, a resulting preselected setpoint is determined (chilled water
flow setpoint), which is passed on to other devices via the “Refrigeration demand"
function block.
For the "Refrigeration request" function to become activated, a refrigeration
distribution zone must be assigned to it on the consumption side:
Main menu > Commissioning > Communication > Distribution zones
Operating line
Range
Factory setting
Refrigeration
distribution zone
----, 1…31
1
11.4.2 Operating principle
The RMB795B central control unit receives the following types of request signals
via bus:
•
Refrigeration demand in %,
e.g. from a room control system "RXB/RXL with cooling coil or chilled ceiling"
•
Valve position in %,
e.g. from a control system "RMU7... as basic type A or U" for an air handling
plant with heating coil/cooling coil
•
Temperature request in °C,
from a primary controller "RMU7… as basic type C"
Purpose
Setting values
Purpose
Settings
Purpose
Activation
Request signals