68 / 144
Siemens
Central control unit RMB795B
CE1P3122en
Building Technologies
Function block: "Room group"
18.01.2012
Main menu > Commissioning > Extra configuration > Room group 1…10 > Room operating
mode
Operating line
Adjustable values / remarks
Operating mode relay
1
---, N.Q1 ... (only free relays) /
assignment of operating mode relays
Operating mode relay
2
---, N.Q1 ... (only free relays) /
assignment of operating mode relays
On the
Settings
menu, the operating mode relay to be energized can be defined
for each room operating mode. This ensures full flexibility, offering a host of
applications.
Main menu > Settings > Room group 1…10 > Room operating mode
Operating line
Adjustable values / remarks
Factory setting
Comfort relay
control
--, R1, R2, R1 + R2
---
Precomfort relay
control
--, R1, R2, R1 + R2
---
Economy relay
control
--, R1, R2, R1 + R2
R2
Protection relay
control
---, R1, R2, R1 + R2
R1 + R2
The adjustable values previously listed under "Settings" mean the following for the
operating mode relay:
Value set
State of relay R1
State of relay R2
---
Normally closed Normally closed
R1 Operating
position
Normally closed
R2 Normally
closed
Operating
position
R1 + R2
Operating
position
Operating
position
The factory setting was chosen to allow for direct connection of the digital outputs
to the digital inputs of the Synco™200 controller.
As the Synco™ 200 controllers do not know operating mode Precomfort, the
central control unit RMB795B switches the Synco™ 200 controllers directly to
Comfort in the event of Precomfort. This setting can be changed to suit individual
needs.
When the digital outputs "Relays 1/2" of a "Room group" function block are
connected to the room operating inputs of 1 or several other "Room group" function
blocks, the following assignments for the "Relays 1/2" outputs are to be made:
Operating line
Assignment
Comfort. R2
Precomfort R1
Economy.
R1 + R2
Protection.
---
Configure operating
mode relays 1 and 2
Settings
Meaning of adjustable
values
Note on factory setting
Connect room
operating modes