Central control unit RMB795B
CE1P3122en
Building Technologies
Distribution zones
18.01.2012
T
RMB795
T
T
RXB
RXB
1
2
3
4
5
H / K changeover
31
21
S
0
1en
bus
Ref
.
Element
1
Heat generation
2
Refrigeration
3
Changeover valve
4
Manual switching to changeover valve and function block "H/C changeover"
5
Forwarding the "Heating / cooling" changeover signal via bus
The central control unit RMS795B does not perform any control functions
(precontrol) here, but only the collection of the demand signals and passing them
on to the relevant source (generation of heat or refrigeration) via function blocks
"Heat demand" and "Refrigeration demand".
11.6.5 Lock time
To prevent the refrigeration machine from switching on immediately following
switch-off of heat generation, a locking time can be set.
Control is locked during the locking time so that no heat or refrigeration demand is
generated and forwarded.
Excessive inlet temperature at the refrigeration machine can damage the
refrigeration machine.
Main menu > Commissioning > Settings > Heating/cooling ch'over >
Operating line
Area
Factory setting
Locking time
00.00...23.50 h.m
00.30 h.m
The locking time acts also after a power drop-related switch-off of the device and
when exiting the Commissioning menu.
11.6.6 Display current state
The current state is displayed in menu "Heating/cooling changeover":
Main menu > H/C changeover
Operating line
Comments
2-pipe heating /cooling
system
Heating / cooling
Key
Note
Setting values