Siemens
Central control unit RMB795B
CE1P3122en
Building Technologies
Commissioning
18.01.2012
5.2.2
Start from the main menu
To navigate from the main menu to commissioning:
Step
Action
Result
1
To select the
Access level
menu, press simultaneously
the
OK
knob and the
ESC
button. Select operating line
Password level
and confirm
with the
OK
knob. Enter the
password (
7
).
The password level is active.
2
Select and confirm operating
line
Commissioning
with the
OK
knob
3
Press the
OK
knob a second
time
On the device side:
•
The application (communication) is
stopped
•
All outputs are set to a defined OFF
state.
On the display:
•
The
Commissioning
menu is
displayed.
5.3
Basic configuration
The
Basic configuration
menu is used to make the following settings:
•
Selecting basic type "B"
•
Assign the central control unit position to the connected extension modules
5.3.1
Select basic type "B"
On the RMB795B central control unit, an empty "Basic configuration" is filed. If
selected, all configurations of the extra configuration will be deleted (for
connections, refer to the configuration diagram).
When selecting a new, empty basic configuration, the following values will not be
deleted:
•
All user-defined texts and business cards.
•
Calendar and time switch room group settings.
•
Basic settings on the
Communication
menu.
•
Current time of day.
•
Trend settings.
•
Values on the
Settings > Device
menu
After selecting basic type "B", a start can be made with a new configuration on the
Extra configuration
menu.
Procedure
Introduction
Selection deletes extra
configuration
Maintained values
New extra configuration