Siemens
Central control unit RMB795B
CE1P3122en
Building Technologies
Communication
18.01.2012
Reception zones
Transmission zones
Inputs (N.X1…A7(2).X4)
Inputs (N.X1…A7(2).X4)
Digital outputs (N.Q1…A7(2).Q5)
Analog outputs (N.Y1…N.Y2)
Main menu > Commissioning > Communication > LTE reception zones >
Operating line
Range
Factory setting
N.X1…A7(2).X4 ---,
1…4095
---
Main menu > Commissioning > Communication > LTE transmission zones >
Operating line
Range
Factory setting
N.X1…A7(2).X4
N.Q1…A7(2).Q5
N.Y1…N.Y2
---, 1…4095
---
Bus signals can be simulated using the "Simulation inputs" function when
commissioning the plant (Section 7.1.4).
The air quality value for an air quality sensor is available on one RMB795B
(device 1). This value is sent as a transmission object via an analog input and
processed by an RMB795B (device 2).
The following transmission and reception zones are engineered for example tasks:
RMB795B, device 1
RMB795B, device 2
Value
Terminal Transmissi
on zone
Terminal Reception
zones
N.Y1
1
N.X1
1
Indoor air quality
= Transmit
= Receive
In RMS705B, device 1, the following is configured:
Main menu > Commissioning > Communication > LTE transmission zones >
Operating line
Range
Factory setting
N.X1 1
In RMS705B, device 2, the following is configured:
Main menu > Commissioning > Extra configuration > Input identifier >
Operating line
Range
Factory setting
N.X1 ppm
Main menu > Commissioning > Communication > LTE reception zones >
Operating line
Range
Factory setting
N.X1 1
KNX
Zone 1
Unit 1
Unit 2
Overview
Setting values
Setting values
Note
Example 1
Data exchange concept
Configuration device 1
Device 2
Configuration diagram