Central control unit RMB795B
CE1P3122en
Building Technologies
Function block: "Room group"
18.01.2012
Operating line
Description
temperature
Zone (Apart.Room)
Geographical zone address of the RXB/RXL room
controller with the lowest room temperature, e.g. 2.4.
For each room group, a high and a low limit value for the room temperature can be
set. If one of the limit values is crossed, a fault status message will be delivered.
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Room group 1...10 > Room temp. supervision >
Operating line
Range
Factory setting
Limit value high
0...50 °C
40 °C
Limit value low
0...50 °C
12 °C
In the fault status message, the geographical zone address is given in the following
format:
"Apartment.Room" (e.g. 6.24).
Based on this address and the planning documentation, the relevant RXB/RXL
room controller can be unambiguously identified.
No.
Text
Effect
45XX
Room temperature > Limit
val. or R'grp 1…10
Non urgent message; must not be
acknowledged.
45XX
Room temperature < Limit
val. or R'grp 1…10
Non urgent message; must not be
acknowledged.
The fault status message texts are predefined. They can be adjusted via operation.
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Room group 1...10 > Room temp. supervision >
Operating line
Range
Factory setting
Room temperature >
Limit val. or R'grp X
20 characters
Room temperature >
Limit val. or R'grp X
Room temperature >
Limit val. and R'grp X
20 characters
Room temperature >
Limit val. and R'grp X
8.7
Optimum start control for individual room
controllers
The function optimum start control preheats or precools the rooms prior to an
automatic change of the operating mode to Comfort to the desired room
temperature. This applies only to switches to a higher operating mode to
Comfort (e.g. a change from Economy to Comfort).
The plant is switched on at the latest possible time required to achieve the setpoint
for the next higher operating mode. The time switch can thus be set to actual room
occupancy. The actual operating period for the plant is significantly reduced
resulting in considerable energy savings.
Limit values
Fault status message
Text adjustments