Siemens
Central control unit RMB795B
CE1P3122en
Building Technologies
Function block: "Room group"
18.01.2012
The values can be influenced as follows:
•
Per room group by summer / winter compensation (refer to the following
subsection)
•
Individually on each RXB/RXL room controller by a QAX room unit, see
functional description of RXB/RXL (Technical Handbook CA2A3899en)
•
The absolute heating/cooling setpoints can be changed individually on each
room controller. It can be influenced accordingly with the setting setpoint priority.
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Room group 1...10 > Room temp. setpoint >
Operating line
Range
Factory setting
Setpoint master
Always, Not in Comfort
mode, Only when changed
Not in Comfort mode
Range
Description
Always
RMB795B is the setpoint master. The absolute setpoints set
locally on the room controller are always overwritten again.
Not in Comfort
mode
The absolute setpoints can be overwritten locally on the
room controller during Comfort operating mode.
The RMB795B is the setpoint master for all other room
operating modes. The absolute setpoints set locally on the
room controller are always overwritten again.
Only when
changed
The user can normally change the absolute setpoints on the
room controller at any time. The setpoints are overwritten on
the room controller, however, when the setpoints are
changed on the central control unit.
8.4.2
Application example, setpoint priority, setpoint master
Types of
building
Setpoint
priority
Setpoint
master
Description of absolute setpoints
Business,
manufacturing
building
yes Always
Setpoints cannot be adjusted in the room,
but rather only by the central control unit
RMB795B.
Setpoints adjusted in the room are reset
after a max. of 15 min to the basis setpoints
for the RMB795B.
Office, school
yes
Not in
Comfort
mode
The setpoints can be adjusted in any manner
in the individual room during the Comfort
phase. They are reset to the basis setpoints
for the RMB, however, as soon as the RMB
operating mode changes to Pcf, Eco.
During the Economy phase, the setpoints
cannot be adjusted, or they are automatically
reset after a max. of 15 min.
Hospital, hotel
yes
Only
when
changed
Setpoints can always be adjusted in the
room, but are overwritten only when the
setpoints are changed by the central control
unit RMB795B (e.g. via WEB by the facility
manager).
Villa no
n/a
The setpoints can be freely adjusted in each
room.
Impact on the
setting values
Setting values